Revolutionary energy efficiency through innovative hybrid technology. On average, 75% energy saved due to speed-regulated components and heat pipe technology. Suitable for international use due to a unique multi-voltage capability. Intuitive operation via touch display. Identical mounting cut-out (external mounting, partial internal mounting and full internal mounting) for four output categories.
Part Number
SK 3186.930
ETIM
Group Code : EG000011
Group Description : Cabinet enclosures
Class Description : Air conditioner (switchgear cabinet)
Class Code : EC000855
Version : 7
€719.10
net
€799.00
Shipping from:
€25.00
1
Payment methods:
Best offer from:
CZTrusted Automa.Net Supplier
Availability:
1 pc.
In-Stock
Updated at: 09-11-2024
Warranty:
24 months
Estimated Delivery:
11-12 November to United Kingdom
Condition:
Used
Used - A previously used item with possible signs of cosmetic wear. It is fully operational and functions as intended, though the original packaging may be missing.
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Air throughput (unimpeded air flow)

External circuit
1,250 m³/h ( 735.7cfm )
Internal circuit
1,250 m³/h ( 735.7cfm )

Dimensions

Width
450 mm ( 18" )
Height
1,600 mm ( 63" )
Depth
294 mm ( 12" )

Total cooling output to DIN EN 14511

L 35 L 35 at 50 Hz
2 kW ( 6,824BTU )
L 35 L 35 at 60 Hz
2 kW ( 6,824BTU )
L 35 L 50 at 50 Hz
1.29 kW ( 4,401BTU )
L 35 L 50 at 60 Hz
1.29 kW ( 4,401BTU )

Temperature range

Storage
-40 °C...+70 °C
Operation (environment)
-20 °C...+60 °C
Heat pipe active mode
-20 °C...+45 °C
Compressor system active mode
+3 °C...+60 °C
Setting range
+20 °C...+50 °C

Specifications

Material
Carbon steel
Color
RAL 7035
Protection category IP to IEC 60 529
Internal circuit IP 55
Options
For remote monitoring and networking of cooling units and chillers, use the Blue e+ Generation IoT Interface, item number 3124.300. Increase machine availability and process safety by remote monitoring of device data, condition, and system messages.
Variant
wall-mounted
Rated output
0.73 kW
Temperature control
e+ controller (factory setting +35 °C)
Permissible operating pressure (p. max.)
24 bar ( 348PSI )
Seasonal energy efficiency ratio (SEER) 50/60 Hz
8.1
ECl@ss 8.0/8.1
27180704
Energy efficiency ratio (EER) 50/60 Hz L35 L35
3,5  / 3,5
ECl@ss 6.0/6.1
27180704

Rated power Pel

L 35 L 35 at 50 Hz
0.57 kW
L 35 L 35 at 60 Hz
0.57 kW
L 35 L 50 at 50 Hz
0.6 kW
L 35 L 50 at 60 Hz
0.6 kW

Refrigerant/cooling medium

Refrigerant
R134a
Quantity
1.15 kg ( 2.5lb. )
Global Warming Potential (GWP)
1,430
CO₂ equivalent (CO₂e)
1.64 t

Documents

Data Sheet

Download