- Mtbf Reliability
- 1300000 H
- Fallback Mode
- configurable || predefined
- Measurement Error
- 0.1 % of full scale 25 °C || <= 0.45 % of full scale - 25...70 °C
- Maximum Conversion Value
- +/- 11.25 V +/- 10 V || 0...24 mA 0...20 mA || 0...24 mA 4...20 mA
- Status Led
- 1 LED (Green) RUN || 1 LED per channel (Green) channel diagnostic || 1 LED (Red) ERR || 1 LED (Red) I/O
- Temperature Drift
- 30 ppm/°C
- Recalibration
- factory calibrated
- Analogue Output Type
- current 0...20 mA || current 4...20 mA || voltage +/- 10 V
- Common Mode Rejection
- 100 dB
- Output Level
- high level
- Supply
- internal power supply via rack
- Minimum Crosstalk Attenuation
- 90 dB
- Net Weight
- 0.144 kg
- Isolation Voltage
- 1400 V DC between channels and ground || 1400 V DC between channels and bus || 750 V DC between channels
- Analogue Output Number
- 2
- Power Consumption In W
- 2.1 W 24 V DC typical || 2.8 W 24 V DC maximum || 0.35 W 3.3 V DC typical || 0.48 W 3.3 V DC maximum
- Load Impedance Ohmic
- <= 600 Ohm 0...20 mA || <= 600 Ohm 4...20 mA || >= 1000 Ohm +/- 10 V
- Detection Type
- open circuit 0...20 mA || open circuit 4...20 mA || short circuit +/- 10 V
- Operating Altitude
- 0...6561.68 ft (0...2000 m) || 2000...5000 m with derating factor
- Analogue Output Resolution
- 15 bits + sign
- Conversion Time
- <= 1 ms