Schneider Electric
GVAS026
1 / 1
Description
Active Mature
TeSys GV electrical trip, MX shunt release, 24V AC 60Hz, for motor circuit breakers GV2, GV3. It trips the circuit breaker when the control voltage is applied in limits 0.7-1.1 Uc with an impulse duration greater than 20ms or a maintained signal. To be mounted on right-hand side of the circuit breaker, connection by screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).- Country of Origin
- CZ
- Part Number
- GVAS026
- Tariff Code
- 85363090
- EAN
- 3389110343588
- UNSPSC
- 39121521
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 1 pc.In-StockUpdated at: 08-11-2024
- Warranty:
- 12 months
- Estimated Delivery:
- On Request
- Condition:
- New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Complementary
- [Uc] Control Circuit Voltage
- 24 V AC 60 Hz
- Control Circuit Voltage Limits
- 0.7...1.1 Un
- Height
- 89 mm
- Tightening Torque
- < 1.4 N.m screw clamp terminals
- Range Compatibility
- TeSys GV2ME || TeSys GV2LE || TeSys GV2L || TeSys GV2P || TeSys GV3L || TeSys GV3P || TeSys Deca
- Hold-In Power Consumption In W
- 1.6-1.6 W
- Net Weight
- 0.105 kg
- Inrush Power In Va
- 14-14 VA AC
- Connections - Terminals
- screw clamp terminals 1 1-2.5 mm²solid || screw clamp terminals 2 1-2.5 mm²solid || screw clamp terminals 1 0.75-2.5 mm²flexible without cable end || screw clamp terminals 2 0.75-2.5 mm²flexible without cable end || screw clamp terminals 1 0.75-1.5 mm²flexible with cable end || screw clamp terminals 2 0.75-1.5 mm²flexible with cable end
- [Ui] Rated Insulation Voltage
- 690 V AC IEC 60947-1 || 600 V AC UL 60947-4-1 || 600 V AC CSA C22.2 No 60947-4-1
- Mechanical Durability
- 10000 cycles with GV3P and GV3L || 30000 cycles with GV2ME and GV2P
- Threshold Tripping Voltage
- 0.75...0.2 Un
- Hold-In Power Consumption In Va
- 5-5 VA AC
- On-Load Factor
- 100 %
- Quantity Per Set
- set of 10
- Operating Time
- 10...15 ms IEC 60947-1
- Color
- dark grey
- Width
- 18 mm
- Depth
- 66 mm
- Inrush Power In W
- 10.5 W
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP2207006
- Sustainable Offer Status
- Green Premium product
- Toxic Heavy Metal Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
- Reach Free Of Svhc
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Circularity Profile
- ENVEOLI2207006
- Eu Rohs Directive
- Compliant
Specifications
- Product Or Component Type
- shunt trip release
- Range
- TeSys || TeSys Deca
- Device Short Name
- GVAS
Contractual warranty
- Warranty
- 18 months
CAD Models
traceparts
Download