- Product Certifications
- IECEE CB Scheme || UL || CSA || UKCA
- [Uc] Control Circuit Voltage
- 400 V AC 50/60 Hz
- [Ue] Rated Operational Voltage
- power circuit 690 V AC 50/60 Hz
- Reactive Power Rating
- 35 kvar 230-230 V AC 50 Hz 60 °C || 63 kvar 400-400 V AC 50 Hz 60 °C || 67 kvar 440-440 V AC 50 Hz 60 °C || 104 kvar 690-690 V AC 50 Hz 60 °C || 30 kvar 230-230 V AC 60 Hz 60 °C || 60 kvar 460-460 V AC 60 Hz 60 °C || 80 kvar 575-575 V AC 60 Hz 60 °C
- Standards
- EN/IEC 60947-1 || EN/IEC 60947-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
- Mounting Support
- DIN rail || plate
- Control Circuit Type
- AC 50/60 Hz
- Device Location In System
- line interruption || inside delta interruption
- Contactor Application
- power factor correction
- Product Or Component Type
- capacitor duty contactor
- Product Name
- TeSys LC1D.K || TeSys Deca
- Range
- TeSys
- Pole Contact Composition
- 3 NO
- Connections - Terminals
- control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || power circuit: connector 1 4-50 mm² - cable stiffness: solid || power circuit: connector 2 4-25 mm² - cable stiffness: solid || power circuit: connector 1 4-50 mm² - cable stiffness: flexible without cable end || power circuit: connector 2 4-25 mm² - cable stiffness: flexible without cable end || power circuit: connector 1 4-50 mm² - cable stiffness: flexible with cable end || power circuit: connector 2 4-16 mm² - cable stiffness: flexible with cable end
- Utilisation Category
- AC-6b
- Maximum Operating Rate
- 240 cyc/h
- Auxiliary Contact Composition
- 1 NO + 2 NC instantaneous
- Tightening Torque
- power circuit 9 N.m connector || control circuit 1.7 N.m screw clamp terminals
- Electrical Durability
- 300000 cycles 400 V || 200000 cycles 690 V
- Poles Description
- 3P
- Device Application
- control
- Device Short Name
- LC1DWK