This Micrologic 6.2 E (Energy) is a 3 poles 3d electronic trip unit used on Compact NSX 250 circuit breakers. This 250A rating electronic trip unit is an optimum choice for all standard and specific applications. It embeds adjustable long time protection against overloads. It provides also adjustable short-time protection and instantaneous protection against short-circuits. It has an additional and adjustable ground fault protection. Micrologic 6.2 E indicates overloads with Alarm LEDs. The green Ready LED flashes if the circuit breaker is ready to trip. Micrologic 6.2 E is equipped with a display module that gives energy measurement and allows fine adjustment settings. This product is part of our EcoStruxure Power architecture if associated with PowerTag NSX and Compact NSX basic frame.- Country of Origin
- FR
- Part Number
- LV431506
- Tariff Code
- 85363090
- EAN
- 3606480017124
- UNSPSC
- 43201542
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 1 pc.In-StockUpdated at: 08-11-2024
- Warranty:
- 12 months
- Estimated Delivery:
- On Request
- Condition:
- New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Specifications
- Network Frequency
- 50/60 Hz
- Trip Unit Name
- Micrologic 6.2 E
- Range Of Product
- ComPact NSX100...250
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz
- Trip Unit Protection Functions
- LSIG
- Network Type
- AC
- Protected Poles Description
- 3t
- Product Or Component Type
- trip unit
- Protection Type
- L : for overload protection (long time) || S : for short time short-circuit protection || I : for instantaneous short-circuit protection || G : for ground fault protection
- Range
- ComPact
- Poles Description
- 3P
- Range Compatibility
- ComPact NSX250
- Device Application
- distribution
- Trip Unit Technology
- electronic
Contractual warranty
- Warranty
- 18 months
Complementary
- [Tg] Ground-Fault Time Delay Adjustment Range
- 0-0.4 s I²t=off || 0.1-0.4 s I²t=on
- [Ig] Ground-Fault Pick-Up Adjustment Range
- 0.2...1 x In In = 40 A || 0.4...1 x In In > 40 A || Ig enable on/off
- Thermal Memory
- 20 minutes before and after tripping
- Earth-Leakage Protection
- without
- Ground-Fault Time Delay Adjustment Type -Tg
- adjustable
- Ground-Fault Pick-Up Adjustment Type
- adjustable
- Type Of Measurement
- energy meter
- Communication Of Data
- maximeters/minimeters || energy metering || protection and alarm settings || time-stamped histories and event tables || maintenance indicators || power quality || instantaneous and demand values || demand current and power
- Long Time Delay Adjustment Type
- adjustable
- Instantaneous Pick-Up Adjustment Type Ii
- adjustable
- Zone Selective Interlocking Zsi
- with
- Electrical Data Recording
- maintenance indicators
- [Tr] Long-Time Delay Adjustment Range
- 15-400 s 1.5 x Ir || 0.35-11 s 7.2 x Ir || 0.5-16 s 6 x Ir
- Short-Time Delay Adjustment Type
- adjustable
- Instantaneous Pick-Up Adjustment Range
- 1.5...12 x In
- Long Time Pick-Up Adjustment Type Ir
- adjustable 9 settings
- Long Time Pick-Up Adjustment Range
- 100...250 A
- [Tsd] Short-Time Delay Adjustment Range
- 0-0.4 s I²t=off || 0.1-0.4 s I²t=on
- [Isd] Short-Time Pick-Up Adjustment Range
- 1.5...10 x Ir
- Display Type
- LCD display
- Short-Time Pick-Up Adjustment Type Isd
- adjustable 9 settings
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP120606EN
- Sustainable Offer Status
- Green Premium product
- California Proposition 65
- WARNING: Cancer and Reproductive Harm - www.P65Warnings.ca.gov
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI120604EN
- Eu Rohs Directive
- Compliant
Environment
- Product Certifications
- EAC || Marine || CCC
- Ambient Air Temperature For Operation
- -25-70 °C
- Standards
- UL 508 || EN/IEC 60947-2
- Ambient Air Temperature For Storage
- -40-85 °C