- Maximum Supply Current For Sensors
- 40 mA < 24 V AC 25 °C || 40 mA < 24 V DC 25 °C || 50 mA 24...240 V AC || 50 mA 24...240 V DC
- Hysteresis
- 5-5 % threshold
- Insulation Resistance
- > 500 MOhm 500 V DC between supply and relay output IEC 60255-5 || > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1 || > 1 MOhm 500 V DC between supply and measurement IEC 60255-5 || > 500 MOhm 500 V DC between supply and relay output IEC 60664-1 || > 500 MOhm 500 V DC between measurement and relay output IEC 60255-5 || > 1 MOhm 500 V DC between supply and measurement IEC 60664-1
- Measurement Error
- +/- 0.1 %/°C with temperature variation || < +/- 1 % over the whole range with voltage variation
- Operating Rate
- <= 360 operations/hour full load
- Status Led
- 1 LED Green power ON || 1 LED Yellow inhibit || 1 LED Yellow relay (R)
- Output Contacts
- 1 C/O
- Contacts Material
- cadmium free
- Polarity
- reversible polarity on DC supply
- Marking
- CE : EMC 89/336/EEC || CE : 73/23/EEC
- Response Time
- 15 ms max (on crossing the threshold)
- Operating Position
- any position without derating
- Input Frequency
- 0.0017-20 Hz
- Threshold Setting
- 10...100 %
- Maximum Switching Voltage
- 250 V AC/DC
- Reset Time
- 50 ms contact S2 in memory mode on time delay || 1 s supply Un in memory mode on time delay
- [Us] Rated Supply Voltage
- 11.5...12.5 V
- Input Compatibility
- 3-wire sensor (E1) PNP or NPN, 12 V, 50 mA || NAMUR sensor (E2), 12 V, 1.5 kOhm || voltage input (E1), 0...30 V, 9.5 kOhm >= 4.5 V <= 1 V || volt-free contact input (E1), 12 V, 9.5 kOhm
- Connections - Terminals
- screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
- [Ui] Rated Insulation Voltage
- 250 V IEC 60664-1
- Overvoltage Category
- III IEC 60664-1
- Supply Voltage Limits
- 20.4-264 V AC/DC
- Mounting Support
- 35 mm symmetrical DIN rail conforming to IEC 60715
- Nominal Output Current
- 5 A
- Mechanical Durability
- 30000000 cycles
- Housing Material
- self-extinguishing plastic
- Control Circuit Voltage Limits
- 15 % + 10 % Un
- Impulse Duration
- >= 5 ms high state || >= 5 ms low state
- Measurement Accuracy
- +/- 10 % of the full scale value
- Width
- 35 mm
- Tightening Torque
- 0.6-1 N.m IEC 60947-1
- Maximum Power Consumption In W
- 3 W DC
- Electrical Durability
- 100000 cycles
- Run-Up Delay At Power-Up
- 0.05 s
- Repeat Accuracy
- +/- 0.5 % input and measurement circuit || +/- 0.5 % time delay
- Supply Frequency
- 50/60 Hz +/- 10 %