- Voltage Range
- 220...480 V phase to phase
- Safety Reliability Data
- MTTFd = 399.5 years || B10d = 360000
- Minimum Switching Current
- 10 mA 5 V DC
- Maximum Measuring Cycle
- 140 ms measurement cycle as true rms value
- Control Circuit Voltage Limits
- 12 % + 10 % Un
- Maximum Switching Current
- 5 A AC || 5 A DC
- Hysteresis
- 2-2 %
- Insulation Resistance
- > 500 MOhm 500 V DC IEC 60255-5 || > 500 MOhm 500 V DC IEC 60664-1
- Measurement Error
- < 1 % over the whole range with voltage variation || 0.05 %/°C with temperature variation
- Operating Rate
- <= 360 operations/hour full load
- Power Consumption In Va
- 0-22 VA 400 V AC 50 Hz
- Output Contacts
- 2 C/O
- Voltage Detection Threshold
- < 194 V
- Adjustment Of Asymmetry Threshold
- 5...15 % of Un selected
- Marking
- CE
- Response Time
- < 200 ms (in the event of a fault)
- Operating Position
- any position without derating
- Utilisation Category
- AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1
- Net Weight
- 0.13 kg
- Maximum Switching Voltage
- 250 V AC || 250 V DC
- Measurement Voltage Limits
- 176-528 V AC
- Reset Time
- 1500 ms at 480 V
- Connections - Terminals
- screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
- [Ui] Rated Insulation Voltage
- 400 V IEC 60664-1
- Overvoltage Category
- III IEC 60664-1
- Supply Voltage Limits
- 194-528 V AC, 3 phase
- Mounting Support
- 35 mm symmetrical DIN rail conforming to IEC 60715
- Nominal Output Current
- 5 A
- Local Signalling
- for power ON LED (green) || for relay ON LED (yellow) || for fault LED (yellow)
- Mechanical Durability
- 30000000 cycles
- Housing Material
- self-extinguishing plastic
- Control Circuit Frequency
- 50...60 Hz +/- 10 %
- Threshold Adjustment Voltage
- -20...-2 % in the range 380...480 V AC || 2...20 % of Un selected || -12...-2 % in the range 220 V AC || +2...+20 % in the range 220...440 V AC || +2...+10 % in the range 480 V AC
- Width
- 35 mm
- Tightening Torque
- 0.6-1 N.m IEC 60947-1
- Electrical Durability
- 100000 cycles
- Run-Up Delay At Power-Up
- 650 ms
- Supply Frequency
- 50/60 Hz +/- 10 %
- Repeat Accuracy
- 0.3 % time delay || 0.5 % input and measurement circuit