- Insulation Between Channels And Logic Bus
- 1500 V for 1 minute
- Cold Swapping
- yes
- Maximum Supply Current For Sensors
- 100 mA per input channels
- Input Impedance
- 400 kOhm
- Insulation Between Channels And Sensor Bus
- 30 V
- Status Led
- 1 LED (Green) module status (RDY) || 1 LED (Red) module error (ERR)
- Hot Swapping Fallback
- yes for standard NIMs
- Differential Linearity
- monotonic
- Integral Linearity
- +/- 0.2 %FS
- Supply
- power distribution module
- Data Format
- IEC 61131-2 || EN 61131-2
- Current Consumption
- 90 mA 5 V DC logic bus
- Marking
- CE
- Fallback Status
- state 0 basic NIMs || user configurable standard NIMs
- Temperature Drift
- +/-0.01 %/°C
- Addressing Requirement
- 2 input words
- Absolute Accuracy Error
- +/- 0.75 % of full scale 25 °C
- Absolute Maximum Input
- 50 V DC
- Maximum Source Impedance
- 1 kOhm
- Update Time
- 22 ms
- Overvoltage Category
- II
- Product Compatibility
- power distribution module STBPDT3100/3105 || mounting base STBXBA1000
- [Us] Rated Supply Voltage
- 24 V DC