- Current Consumption
- 160 mA contactor sealed || 160 mA contactor closing
- Power Dissipation In W
- 11.8 W at Ie AC-3
- Power Dissipation Per Pole
- 2.9 W AC-3 - Ith 38 A || 3.2 W AC-1 - Ith 40 A
- Average Impedance
- 2 mOhm - Ith 40 A 50 Hz
- Reset
- remotely or automatically
- [Ith] Conventional Free Air Thermal Current
- 40 A (at 50 °C)
- [Uc] Control Circuit Voltage
- 24 V DC supplied by the bus coupler
- Rated Breaking Capacity
- 550 A at 440 V conforming to IEC 60947
- Product Or Component Type
- motor starter
- Irms Rated Making Capacity
- 550 A at 440 V conforming to IEC 60947
- Product Name
- TeSys island
- Thermal Overload Class
- class 5…30
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947-1
- Range
- TeSys
- Device Presentation
- direct starter connected to an automation controller through a bus coupler || operational only when connected to a bus coupler
- Motor Starter Type
- direct on line
- Utilisation Category
- AC-1 || AC-2 || AC-3 || AC-4
- Function Available
- upstream voltage presence detection || electrical line and load protection || power and energy monitoring when connected with TPRVM voltage module
- [Ie] Rated Operational Current
- 38 A (at <50 °C) at <= 440 V AC-3 || 40 A (at <50 °C) at <= 440 V AC-1
- Overvoltage Category
- III for Ue <= 480 V || II for Ue <= 690 V
- Thermal Protection Adjustment Range
- 0.76-38 A
- Product Compatibility
- TPRBC bus coupler || TPRVM voltage interface module
- [Ue] Rated Operational Voltage
- <= 480 V AC 47...63 Hz for overvoltage cat. III || <= 690 V AC 47...63 Hz for overvoltage cat. II
- Maximum Horse Power Rating
- 2 hp at 120 V AC 60 Hz for 1 phase motors || 5 hp at 240 V AC 60 Hz for 1 phase motors || 10 hp at 208 V AC 60 Hz for 3 phase motors || 10 hp at 240 V AC 60 Hz for 3 phase motors || 20 hp at 480 V AC 60 Hz for 3 phase motors || 25 hp at 600 V AC 60 Hz for 3 phase motors
- Motor Power Kw
- 9 kW at 230 V 50 Hz (AC-3) || 18.5 kW at 380...415 V 50 Hz (AC-3) || 18.5 kW at 440 V 50 Hz (AC-3) || 18.5 kW at 500 V 50 Hz (AC-3) || 18.5 kW at 690 V 50 Hz (AC-3)
- [Ui] Rated Insulation Voltage
- 690 V IEC 60947-4-1 || 600 V UL 60947-4-1 || 600 V CSA C22.2 No 60947-4-1
- Device Short Name
- TPRST
- Poles Description
- 3P 3 NO
- [Icw] Rated Short-Time Withstand Current
- 430 A 40 °C - 1 s || 310 A 40 °C - 10 s || 150 A 40 °C - 1 min || 60 A 40 °C - 10 min