1 / 1
thumbnail

Description

Active Mature
These TeSys VLS disconnect switches are for integration into control systems in applications like material handling, HVAC, pumping, solar energy, mining and many more. This family of disconnect switches has switches ranging from 16A to 125A. The 16A, 25A, 32A, 40A and 63A disconnect switches are UL508 motor disconnect switches rated. The 30A, 63A, 80A, 100A and 125A disconnect switches are UL98 non fusible disconnect switch rated. This 25A disconnect switch has 3 normally open poles and mounts directly in the enclosure door. Per UL and CSA this this disconnect switch has a 1.5 HP rating at 120 VAC and a 3 HP at 240 VAC single phase. Per UL and CSA this disconnect switch has a 7.5 HP rating at 200 to 208 VAC and 240 VAC, a 15 HP rating at 480 VAC and a 20 HP rating at 600 VAC three phase. Per UL508A this this disconnect switch has up to a 5 kA at 600 V short circuit current rating (SCCR) with a 30A Type RK5 fuse maximum. Per IEC requirements, this disconnect switch has a 11 kW rating at 400 V, a 15 kW rating at 500 V and a 22 kW rating at 690V three phase. The screw clamp terminals will accept 10 mm solid or 16 mm stranded wire. The clamps will also accept solid or stranded wire from 18 AWG to 6 AWG. This disconnect switch is 3.07 inches tall, 1.77 inches wide and 2.87 inches deep. The switch weighs 0.30 lbs. There are many handles and accessories available this TeSys VLS disconnect switch. This TeSys VLS disconnect switch is UL Listed per UL60947-4-1, CSA certified per CSA 22.2 and meets IEC 60947-3 requirements.
Country of Origin
IT
Part Number
VLS3P025D1
Tariff Code
85365080
EAN
3606481156525
UNSPSC
39122233
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
Reach Free Of Svhc
Yes
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Eu Rohs Directive
Compliant

Complementary

Network Frequency
50/60 Hz
[Ue] Rated Operational Voltage
600 V AC 50/60 Hz UL 508
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz
Height
73 mm
Intermittent Duty Class
class 120 - 60 %
[Ith] Conventional Free Air Thermal Current
25 A (at 55 °C)
Mounting Support
door
Network Type
AC
[Ithe] Conventional Enclosed Thermal Current
25 A
Net Weight
0.135 kg
Performance Level
high performance
[Uimp] Rated Impulse Withstand Voltage
8 kV
Making Capacity
250 A 690 V AC-23A || 37.5 A 690 V AC-21A || 75 A 690 V AC-22A
Connections - Terminals
power circuit screw clamp terminals 10-10 mm² solid || power circuit screw clamp terminals 16-16 mm² flexible - without cable end
Contacts Type And Composition
3 NO
[Icm] Rated Short-Circuit Making Capacity
1128 A 690 V
Electrical Durability
100000 cycles AC-21A
[Ie] Rated Operational Current
25 A Ue: 600 V UL 508 || 25 A AC-21A Ue: 400 V || 25 A AC-21A Ue: 500 V || 25 A AC-21A Ue: 690 V || 25 A AC-22A Ue: 400 V || 25 A AC-22A Ue: 500 V || 25 A AC-22A Ue: 690 V || 25 A AC-23A Ue: 400 V || 25 A AC-23A Ue: 500 V || 25 A AC-23A Ue: 690 V
Mechanical Durability
100000 cycles
Poles Description
3P
Color
Gray
Width
45 mm
Tightening Torque
power circuit 1.8-2 N.m screw clamp terminals
Depth
78 mm
Breaking Capacity
37.5 A 690 V AC-21A) || 75 A 690 V AC-22A) || 200 A 690 V AC-23A)
Rated Operational Power In W
11 kW 400 V AC-23A) || 15 kW 500 V AC-23A) || 22 kW 690 V AC-23A)
Rated Conditional Short-Circuit Current
50 kA 400 V 25 A gG
[Icw] Rated Short-Time Withstand Current
800 A 690 V 1 s

Specifications

Product Or Component Type
switch body
Product Name
TeSys VARIO LS
Range
TeSys
Device Short Name
VLS3P

Environment

Product Certifications
cULus || GL
Ambient Air Temperature For Operation
-25-55 °C
Standards
UL 508 || CSA C22.2 No 14 || IEC 60947-3
Ip Degree Of Protection
IP20 conforming to IEC 60529
Mechanical Robustness
vibrations 2...100 Hz Fc 0.7 g) IEC 60068-2-6 || shocks 11 ms Ea 15 gn) IEC 60068-2-27
Fire Resistance
960 °C IEC 60695-2-11