Schneider Electric

XMLA002A2S12

1 / 1
thumbnail

Description

This XMLA electromechanical pressure switch has a fixed differential for detection of a single threshold and a zinc alloy body with a range scale window. This pressure switch is designed for detection of a single pressure threshold in air, fresh water, hydraulic oils, corrosive fluids and viscous products up to 70°C. It is fixed directly on tubage. It provides zinc alloy enclosure for robust performance. 8 million cycles mechanical durability for minimum required maintenance on your pressurized fluid circuits. It complies with CCC, EN/IEC 60947-5-1, CSA C22.2 No.14, LROS, UL 508, EAC, BV.
Country of Origin
CZ
Part Number
XMLA002A2S12
Tariff Code
90322000
EAN
3389110748482
UNSPSC
39122210
Payment methods:
Best offer from:
DETrusted Automa.Net Supplier
Availability:
1 pc.
In-Stock
Updated at: 08-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Specifications

Contacts Type And Composition
1 C/O
Pressure Sensor Type
electromechanical pressure sensor
Pressure Actuator
diaphragm
Electrical Connection
screw-clamps terminals, 1 x 0.5...2 x 2.5 mm²
Range Of Product
Telemecanique Pressure sensors XM
Line Rated Current
3 A, B300, AC-15 (Ue = 120 V)EN/IEC 60947-5-1 || 1.5 A, B300, AC-15 (Ue = 240 V)EN/IEC 60947-5-1 || 0.1 A, R300, DC-13 (Ue = 250 V)EN/IEC 60947-5-1
Pressure Switch Type Of Operation
detection of 1 single threshold
Cable Entry
cable gland 7-13 mm
Product Or Component Type
electromechanical pressure sensor
Adjustable Range Of Switching Point On Falling Pressure
0.02-2.37 bar
Materials In Contact With Fluid
nitrile || zinc alloy
Local Display
with
Fluid Connection Type
G 1/4 (female) ISO 228
Pressure Sensor Size
2.5 bar
Controlled Fluid
air 0-70 °C) || fresh water 0-70 °C) || hydraulic oil 0-70 °C)
Awg Gauge
AWG 20...AWG 14
Scale Type
fixed differential
Electrical Circuit Type
control circuit
Enclosure Material
zinc alloy
Adjustable Range Of Switching Point On Rising Pressure
0.15-2.5 bar
Maximum Permissible Accidental Pressure
9 bar
Destruction Pressure
18 bar
Device Short Name
XMLA

Contractual warranty

Warranty
18 months

Complementary

Repeat Accuracy
2 %
Height
158 mm
Terminal Block Type
4 terminals
Short-Circuit Protection
10 A cartridge fuse gG (gl)
Natural Differential At High Setting
0.13 bar +/- 0.03 bar)
Contacts Material
silver contacts
Auxiliary Contacts Operation
snap action
Net Weight
0.995 kg
[Uimp] Rated Impulse Withstand Voltage
6 kV EN/IEC 60947-1
Maximum Permissible Pressure - Per Cycle
5 bar
Maximum Operating Rate
120 cyc/mn
[Ui] Rated Insulation Voltage
300 V UL 508 || 500 V EN/IEC 60947-1 || 300 V CSA C22.2 No 14
Setting
external
Mechanical Durability
8000000 cycles
Width
35 mm
Depth
77.5 mm
Natural Differential At Low Setting
0.13 bar +/- 0.03 bar)
Maximum Resistance Across Terminals
25 mOhm IEC 255-7 category 3 || 25 mOhm NF C 93-050 method A

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP110914EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Product Certifications
UL || CCC || BV || LROS (Lloyds register of shipping) || EAC || CSA
Ambient Air Temperature For Operation
-25-70 °C
Standards
CE || UL 508 || CSA C22.2 No 14 || EN/IEC 60947-5-1
Vibration Resistance
4 gn 30-500 Hz)IEC 60068-2-6
Shock Resistance
50 gn IEC 60068-2-27
Ip Degree Of Protection
IP66 conforming to EN/IEC 60529
Ambient Air Temperature For Storage
-40-70 °C
Protective Treatment
TC standard version
Electrical Shock Protection Class
class I IEC 1140 || class I IEC 536 || class I NF C 20-030
Operating Position
any position