Specifications

Pressure Sensor Type
pressure transmitter
Type Of Output Signal
analogue
Range Of Product
Telemecanique Pressure sensors XM
Electrical Connection
1 male connector EN 175301-803-A (ex DIN43650) 3 pins
Pressure Sensor Size
250-250 bar
Product Or Component Type
electronic pressure sensors
Type Of Packing
individual
Local Display
without
Pressure Sensor Name
XMLP
Current Consumption
< 23 mA
Fluid Connection Type
R 1/4 (male) EN 10226
Analogue Output Function
4...20 mA, 2-wire
Controlled Fluid
fresh water 0-135 °C) || air -40-135 °C) || hydraulic oil -40-135 °C) || gas -40-135 °C) || refrigeration fluid -40-135 °C)
Quantity Per Set
set of 1
Electrical Circuit Type
control circuit
[Us] Rated Supply Voltage
12...24 V DC SELV 7-33 V)

Complementary

Accuracy
0.1 % of the measuring range
Diameter
26 mm
[Uimp] Rated Impulse Withstand Voltage
0.5 kV
Drift Of The Zero Point
+/- 0.02 % of measuring range/°K
Electromagnetic Compatibility
electrostatic discharge immunity test EN/IEC 61000-4-2 8 kV air, 4 kV contact || 1.2/50 µs shock waves immunity test EN/IEC 61000-4-5 1 kV 42 Ohm || immunity to magnetic fields EN/IEC 61000-4-8 100 A/m 50 Hz || electrical fast transient/burst immunity test EN/IEC 61000-4-4 4 kV || susceptibility to electromagnetic fields EN/IEC 61000-4-3 10 V/m 80...3000 MHz || radiated RF fields EN/IEC 61000-4-6 10 V 0.01...80 MHz
Materials In Contact With Fluid
stainless steel AISI 316L
Length
58.5 mm
Net Weight
0.11 kg
Mechanical Durability
10000000 cycles
Operating Position
any position
Measurement Accuracy
+/- 0.5 % of the measuring range
Protection Type
load short-circuit || reverse polarity
Drift Of The Sensitivity
+/- 0.02 % of measuring range/°K
Maximum Permissible Accidental Pressure
750 bar
Destruction Pressure
1500 bar
Response Time On Output
<= 2 ms 10...90 % of full scale
Pressure Setting Range
0-250 bar

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1511013EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Product Certifications
CE || cULus || RCM || EAC
Ambient Air Temperature For Operation
-30-85 °C
Standards
EN/IEC 61326-2-3 || NSF ANSI 61
Shock Resistance
100 gn 11 ms EN/IEC 60068-2-27
Vibration Resistance
20 gn 15-2000 Hz) EN/IEC 60068-2-6
Ip Degree Of Protection
IP65 conforming to EN/IEC 60529
Ambient Air Temperature For Storage