Description

Active Mature
Country of Origin
CH
Part Number
XMLPM15RD73F
Tariff Code
9026204000
EAN
41111926
UNSPSC
41111926
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Pressure Sensor Type
pressure transmitter
Type Of Output Signal
analogue
Range Of Product
Telemecanique Pressure sensors XM
Electrical Connection
1 male connector M12 4 pins
Pressure Sensor Size
-14.5-15 psi
Product Or Component Type
electronic pressure sensors
Type Of Packing
individual
Local Display
without
Pressure Sensor Name
XMLP
Current Consumption
< 7 mA
Fluid Connection Type
1/4" - 18 NPT (male)
Analogue Output Function
0...10 V, 3-wire
Controlled Fluid
fresh water 0-125 °C) || air -15-125 °C) || gas -15-125 °C) || hydraulic oil -15-125 °C)
Quantity Per Set
set of 1
Electrical Circuit Type
control circuit
[Us] Rated Supply Voltage
24 V DC SELV 12-33 V)

Complementary

Accuracy
0.1 % of the measuring range
Diameter
26 mm
[Uimp] Rated Impulse Withstand Voltage
0.5 kV
Repeat Accuracy
+/- 0.25 % of the measuring range
Drift Of The Zero Point
+/- 0.02 % of measuring range/°K
Electromagnetic Compatibility
susceptibility to electromagnetic fields EN/IEC 61000-4-3 10 V/m 80...1000 MHz || electrical fast transient/burst immunity test EN/IEC 61000-4-4 2 kV || radiated RF fields EN/IEC 61000-4-6 10 V 0.15...80 MHz || electrostatic discharge immunity test EN/IEC 61000-4-2 8 kV air, 4 kV contact || 1.2/50 µs shock waves immunity test EN/IEC 61000-4-5 1 kV 42 Ohm || immunity to magnetic fields EN/IEC 61000-4-8 100 A/m 50 Hz
Materials In Contact With Fluid
stainless steel AISI 316L || ceramic || fluorocarbon FPM
Length
30.2 mm
Net Weight
0.075 kg
Mechanical Durability
10000000 cycles
Operating Position
any position
Measurement Accuracy
+/- 0.5 % of the measuring range
Protection Type
reverse polarity || load short-circuit
Drift Of The Sensitivity
+/- 0.02 % of measuring range/°K
Maximum Permissible Accidental Pressure
44 psi
Destruction Pressure
73 psi
Response Time On Output
<= 2 ms 10...90 % of full scale
Pressure Setting Range
-14.5-15 psi

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1511013EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Product Certifications
RCM || EAC || CE || cULus
Ambient Air Temperature For Operation
-30-85 °C
Standards
NSF ANSI 61 || EN/IEC 61326-2-3
Shock Resistance
100 gn 11 ms EN/IEC 60068-2-27
Vibration Resistance
20 gn 10-2000 Hz) EN/IEC 60068-2-6
Ip Degree Of Protection
IP65 conforming to EN/IEC 60529 || IP67 conforming to EN/IEC 60529 || IP69K conforming to DIN 40050
Ambient Air Temperature For Storage
-50-100 °C

Documents

Data Sheet

Download