1 / 1
thumbnail

Description

Active Mature
This product is part of the XC Standard range, an offer of limit switches. This programmable receiver is equipped with 2 buttons and 6 LED indicators (power ON, reception signal and output active). It has 4 PNP output contacts and has 2.4GHz ZigBee green power communication port protocol. It is available with 1A fuse type fast blow short-circuit protection. It is a programmable receiver with nominal output current of 0.8A at 24V DC, maximum switching current of 200mA DC, rated supply voltage of 24V DC and maximum power consumption of 26W DC. Receiver unit has 2 channels per receiver. It supports 35mm symmetrical DIN rail mount conforming to EN/IEC 60715, mounting plate. It is an IP20 rated product. The programmable receiver is made of self-extinguishing plastic. Its dimensions are 36mm (Width) x 75mm (Depth) x 108mm (Height) and weighs 0.13kg. It is used for interface to PLC applications. This product is certified by CE. It meets EN/IEC 60947-5-1 and EN/IEC 60947-1 standards. It is compatible with radio transmitter XZBWE112A24. Limit switches for contact sensing of inflexible objects. High quality of products and worldwide availability guarantee in a short delivery time. A comprehensive offer of contacts for a simpler and safer machine design. Ex OsiSwitch, IEC standard format limit switches consist of products designed according to EN 50047, EN 50041 as well as popular XCM and XCKM miniature and classic limit switches ranges.
Country of Origin
FR
Part Number
XZBWR2STT24
Tariff Code
85176200
EAN
3389119623964
Payment methods:
Best offer from:
GBTrusted Automa.Net Supplier
Availability:
1 pc.
In-Stock
Updated at: 21-10-2024
Estimated Delivery:
On Request
Condition:
New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Specifications

Product Or Component Type
programmable receiver
Product Compatibility
radio transmitter XZBWE
Device Application
interface to PLC

Complementary

[Us] Rated Supply Voltage
24 V DC - 15...20 %
Minimum Switching Current
10 mA
Height
108 mm
Maximum Switching Current
200 mA DC
Short-Circuit Protection
1 A fuse fast blow
[Uimp] Rated Impulse Withstand Voltage
0.8 kV
Status Led
1 LED Green power ON || 1 LED green and yellow reception signal || 4 LEDs Green output active
Output Contacts
4 PNP
Electrical Connection
1 conductor cable 0.14-2.5 mm² AWG 26...AWG 14 solid without cable end IEC 60947-1 || 2 conductors cable 0.14-1.5 mm² AWG 26...AWG 16 solid without cable end IEC 60947-1 || 1 conductor cable 0.14-4 mm² AWG 26...AWG 12 flexible with cable end IEC 60947-1 || 2 conductors cable 0.14-1.5 mm² AWG 26...AWG 16 flexible with cable end IEC 60947-1
Communication Port Protocol
Zigbee green power 2.4 GHz
Response Time
< 30 ms after sensor change
Marking
CE
Operating Position
any position without derating
Starting Time
<= 400 ms
Utilisation Category
DC-13 EN/IEC 60947-5-1
Net Weight
0.13 kg
Maximum Voltage Drop
<2 V 200 mA)
Time Delay Range
0.5 s - 15...15 %)
Nominal Output Current
0.8 A 24 V DC
Rated Short-Duration Power Frequency Withstand Voltage
1 kV 50 Hz EN/IEC 60947-5-1
Maximum Sensing Distance
100 m in free field || 25 m in a metal enclosure
Breaking Capacity
4.8 W per output)
Maximum Number Of Transceivers
ZigBee <2
Mounting Support
35 mm symmetrical DIN rail conforming to EN/IEC 60715 || mounting plate
Housing Material
self-extinguishing plastic
Function Of Module
receiver unit for remote sensor
Width
36 mm
Output Type
transistor PNP
Depth
75 mm
Tightening Torque
0.5-1 N.m EN/IEC 60947-1
Maximum Power Consumption In W
26 W DC
Number Of Channels
2 per receiver

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Diisononyl phthalate (DINP), which is known to the State of California to cause cancer, and Di-isodecyl phthalate (DIDP), which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Eu Rohs Directive
Pro-active compliance (Product out of EU RoHS legal scope)

Environment

Standards
EN/IEC 60947-5-1 || EN/IEC 60947-1
Shock Resistance
10 gn 16 ms) 6000 shocks IEC 60068-2-27
Vibration Resistance
+/- 7.5 mm 5-14 Hz)IEC 60068-2-6 || 2 gn 8-150 Hz)IEC 60068-2-6
Insulation Resistance
> 500 MOhm 500 V DC NF C 20-030
Ip Degree Of Protection
IP20 IEC 60529 casing) || IP20 IEC 60529 terminals)
Electromagnetic Compatibility
immunity for industrial environments conforming to EN/IEC 61000-6-2 || conducted emission conforming to ETSI EN 301 489-17 || radiated emission conforming to ETSI EN 300 328 || electrical fast transient/burst immunity test 1 kV PNP output wires conforming to IEC 61000-4-4 || 1.2/50 µs shock waves immunity test 0.5 kV differential mode conforming to IEC 61000-4-5 || 1.2/50 µs shock waves immunity test 1 kV common mode conforming to IEC 61000-4-5 || immunity to microbreaks and voltage drops 7 ms conforming to IEC 61000-4-11 || conducted and radiated emissions class B conforming to CISPR 22 || electrostatic discharge immunity test 8 kV in free air (in insulating parts) conforming to IEC 61000-4-2 || electrostatic discharge immunity test 6 kV on contact (on metal parts) conforming to IEC 61000-4-2 || susceptibility to electromagnetic fields 10 V/m, 80 MHz...1 GHz at 3 m conforming to IEC 61000-4-3 || susceptibility to electromagnetic fields 3 V/m, 1.4 MHz…2 GHz at 3 m conforming to IEC 61000-4-3 || electrical fast transient/burst immunity test 2 kV power supply wires conforming to IEC 61000-4-4 || conducted RF disturbances 10 V conforming to IEC 61000-4-6 || radiated emission conforming to ETSI EN 301 489-17
Pollution Degree
2 IEC 60664-1
Surge Withstand
0.5 kV differential mode IEC 61000-4-5 || 1 kV common mode IEC 61000-4-5
Ambient Air Temperature For Storage
-40-70 °C
Overvoltage Category
III IEC 60664-1
Relative Humidity
90-90 % -20-55 °C, without condensation ETSI EN 300 328
[Ui] Rated Insulation Voltage
60 V IEC 60664-1