Wago
2006-1631/1099-867
1 / 2
- Part Number
- 2006-1631/1099-867
- Tariff Code
- 85369095000
- UPC
- 4050821213321
- ETIM
- Group Code : EG000012
- Group Description : Terminal blocks
- Class Description : Fuse terminal block
- Class Code : EC000899
- Version : 7
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Ratings Per Iec/En
- Ratings per
- IEC/EN 60947-7-3
- Ratings (note)
- Electrical ratings are given by the fuse and blown fuse indication.
- Nominal voltage (III/3)
- 800 V
- Rated impulse voltage (III/3)
- 8 kV
- Rated current
- 10 A
- Note (rated current)
- Leakage current in case of a blown fuse: LED 2 mA
- Operation status indicator
- 120 V
- Legend (ratings)
- (III / 3) ≙ Overvoltage category III / Pollution degree 3
Environmental Requirements
- Processing temperature
- -35 … +85 °C
- Continuous operating temperature
- -60 … +105 °C
Physical Data
- Width
- 10.4 mm / 0.409 inches
- Height
- 96.3 mm / 3.791 inches
- Depth from upper-edge of DIN-rail
- 59 mm / 2.323 inches
Material Data
- Note (material data)
- <a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
- Color
- Gray
- Material group
- I
- Insulation material
- Polyamide (PA66)
- Flammability class per UL94
- V0
- Fire load
- 0.588 MJ
- Weight
- 29.350 g
Mechanical Data
- Mounting type
- DIN-35 rail
- Marking level
- Center/side marking
General
- Fuse receptacle
- Pivoting
- Fuse type
- Cylindrical fuse; 1/4" x 1 1/4"
Specifications
- Product Group Code
- 0022
Commercial Data
- Packaging type
- Box
- Country of origin
- DE
- GTIN
- 4050821213321
- Customs tariff number
- 85369095000
Ratings Per Csa
- Approvals per
- CSA 22.2 No 158
- Rated voltage CSA (Use Group B)
- 600 V
- Rated current CSA (Use Group B)
- 15 A
- Rated voltage CSA (Use Group C)
- 600 V
- Rated current CSA (Use Group C)
- 15 A
Power Loss
- Power loss (max.) Pl (max.) (note)
- When selecting glass cartridge fuses, make sure that the maximum power loss listed below is not exceeded. The power loss is determined according to IEC or EN 60947-7-3/VDE 0611-6 at 23°C. The temperature rise of the terminal block must be checked according to their application and mounting. Higher ambient temperatures represent an additional impact on miniature fuses. Therefore, in such applications, the rated current must be reduced if necessary. More details are available from the manufacturers.
- Power loss Pl max. overload and short-circuit protection (individual arrangement)
- 2.5 W
- Power loss Pl max. overload and short-circuit protection (group arrangement)
- 2.5 W
- Power loss Pl max. short-circuit protection (individual arrangement)
- 2.5 W
- Power loss Pl max. short-circuit protection (group arrangement)
- 2.5 W
Connection 1
- Connection technology
- Push-in CAGE CLAMP®
- Actuation type
- Operating tool
- Connectable conductor materials
- Copper
- Nominal cross-section
- 6 mm²
- Solid conductor
- 0.5 … 10 mm² / 20 … 8 AWG
- Solid conductor; push-in termination
- 1 … 10 mm² / 14 … 8 AWG
- Fine-stranded conductor
- 0.5 … 10 mm² / 20 … 8 AWG
- Fine-stranded conductor; with insulated ferrule
- 0.5 … 6 mm² / 20 … 10 AWG
- Fine-stranded conductor; with ferrule; push-in termination
- 2.5 … 6 mm² / 16 … 10 AWG
- Note (conductor cross-section)
- Depending on the conductor characteristic, a conductor with a smaller cross-section can also be inserted via push-in termination.
- Strip length
- 13 … 15 mm / 0.51 … 0.59 inches
- Wiring direction
- Front-entry wiring
Ratings Per Ul 1059
- Approvals per
- UL 1059
- Rated voltage UL (Use Group B)
- 120 V
- Rated current UL (Use Group B)
- 15 A
- Rated voltage UL (Use Group C)
- 120 V
- Rated current UL (Use Group C)
- 15 A