Wago
285-147
1 / 2
- Part Number
- 285-147
- Tariff Code
- 85369010000
- UPC
- 4055143608336
- ETIM
- Group Code : EG000012
- Group Description : Terminal blocks
- Class Description : Feed-through terminal block
- Class Code : EC000897
- Version : 7
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Ratings Per Iec/En
- Ratings per
- IEC/EN 60947-7-1
- Nominal voltage (III/3)
- 1000 V
- Rated impulse voltage (III/3)
- 8 kV
- Rated current
- 150 A
- Legend (ratings)
- (III / 3) ≙ Overvoltage category III / Pollution degree 3
Environmental Requirements
- Processing temperature
- -35 … +85 °C
- Continuous operating temperature
- -60 … +105 °C
Physical Data
- Width
- 20 mm / 0.787 inches
- Height from the surface
- 94 mm / 3.7 inches
- Depth
- 130 mm / 5.118 inches
Material Data
- Note (material data)
- <a href="https://www.wago.com/us/material-specifications" href="_blank">Information on material specifications can be found here</a>
- Color
- Dark gray-yellow
- Material group
- I
- Insulation material
- Polyamide (PA66)
- Flammability class per UL94
- V0
- Fire load
- 2.040 MJ
- Weight
- 164.610 g
Mechanical Data
- Mounting type
- Mounting flange
- Marking level
- Side marking
Specifications
- Product Group Code
- 0001
Commercial Data
- Packaging type
- Box
- Country of origin
- PL
- GTIN
- 4055143608336
- Customs tariff number
- 85369010000
Ratings Per Csa
- Approvals per
- CSA 22.2 No 158
- Rated voltage CSA (Use Group B)
- 600 V
- Rated current CSA (Use Group B)
- 150 A
- Rated voltage CSA (Use Group C)
- 600 V
- Rated current CSA (Use Group D)
- 150 A
Power Loss
- Power loss, per pole (potential)
- 4.725 W
- Rated current IN for specified power loss
- 150 A
- Resistance value for specified, current-dependent power loss
- 0.0001 Ω
Connection 1
- Connection technology
- POWER CAGE CLAMP
- Actuation type
- T-wrench; 8 mm
- Connectable conductor materials
- Copper
- Solid conductor
- 10 … 50 mm² / 8 … 1/0 AWG
- Stranded conductor
- 10 … 70 mm² / 8 … 2/0 AWG
- Fine-stranded conductor
- 10 … 70 mm² / 8 … 2/0 AWG
- Fine-stranded conductor; with insulated ferrule
- 10 … 50 mm² / 8 … 1/0 AWG
- Fine-stranded conductor; with uninsulated ferrule
- 10 … 50 mm² / 8 … 1/0 AWG
- Strip length
- 30 mm / 1.18 inches
- Wiring direction
- Side-entry wiring
Ratings Per Ul 1059
- Approvals per
- UL 1059
- Rated voltage UL (Use Group B)
- 600 V
- Rated current UL (Use Group B)
- 150 A
- Rated voltage UL (Use Group C)
- 600 V
- Rated current UL (Use Group C)
- 150 A