- Number of analog inputs
- 4
- Total number of channels (module)
- 4
- Signal type
- Resistance measurement || Potentiometer positions
- Signal type (configurable)
- Yes
- Sensor connection
- 4 x (2-wire); 2 x (3-wire)
- Data width
- 4 (2) x 16-bit data; 4 (2) x 8-bit control/status (optional)
- Resolution (over entire range)
- 0.1 °C
- Conversion time (typ.)
- 320 ms
- Measurement error (25 °C)
- ≤ 1 K within the entire temperature range, ≤ 0.5 K within the temperature range (−30 … +120 °C, Pt 1000)
- Temperature coefficient
- ≤ 20 ppm/K
- Measuring current (typ.)
- ≤ 350 µA
- Measurement repetition rate (standard)
- 1.1 s
- Measurement repetition rate (2-channel/2-conductor)
- 0.63 s
- Response time (max.)
- 4 s
- Sensor types
- Pt100; Configurable: Pt200, Pt500, Pt1000, Ni100, Ni120, Ni1000; Potentiometer (2-channel operation only): 10R … 1k2, 10R … 5k0
- Temperature range
- −200 … +850 °C (Pt100), −60 … +300 °C (Ni 100, Ni 1000), −60 … +250 °C (Ni 1000 TK5000), −80 … +260 °C (Ni 120)
- Configuration options
- WAGO-I/O-CHECK || CODESYS Library || e!COCKPIT
- Supply voltage (system)
- 5 VDC; via data contacts
- Current consumption (5 V system supply)
- 50 mA
- Supply voltage (field)
- 24 VDC (-25 … +30 %); via power jumper contacts (power supply via blade contact; transmission via spring contact)
- Isolation
- 500 V system/field
- Indicators
- LED (A, B, E, F) green: Function AI 1 … AI 4; LED (C, D, G, H) red: Error AI 1 … AI 4
- Number of incoming power jumper contacts
- 2
- Number of outgoing power jumper contacts
- 2
- Current carrying capacity (power jumper contacts)
- 10 A