Wago

750-606

Power Supply; 24 VDC; Diagnostics; Intrinsically safe
750-606
750-606
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
€377.61
1
Payment methods:
A total of 554 Parts In-Stock from 20 Distributors

Additional Information

Part Number
750-606
UPC
4045454961909
Tariff Code
85389091890
ETIM
Group Code : EG000024
Group Description : PLC's
Class Description : Fieldbus, decentr. periphery - power supply/segment module
Class Code : EC001600
Version : 7

Environmental Requirements

Ambient temperature (operation)
0 … +55 °C
Ambient temperature (storage)
-25 … +85 °C
Protection type
IP20
Pollution degree
2 per IEC 61131-2
Operating altitude
0 … 2000 m / 0 … 6562 ft
Mounting position
Horizontal (standing/lying); vertical
Relative humidity (without condensation)
95 %
Vibration resistance
4g per IEC 60068-2-6
Shock resistance
15g per IEC 60068-2-27
EMC immunity to interference
Per EN 61000-6-2, marine applications
EMC emission of interference
Per EN 61000-6-3, marine applications
Exposure to pollutants
Per IEC 60068-2-42 and IEC 60068-2-43
Permissible H2S contaminant concentration at a relative humidity 75 %
10 ppm
Permissible SO2 contaminant concentration at a relative humidity 75 %
25 ppm

Connection Data

Connection technology: field supply
2 x CAGE CLAMP®
Connection type 1
Field supply
Solid conductor
0.08 … 1.5 mm² / 28 … 14 AWG
Fine-stranded conductor
0.08 … 1.5 mm² / 28 … 14 AWG
Strip length
5 … 6 mm / 0.2 … 0.24 inches

Physical Data

Width
48 mm / 1.89 inches
Height
100 mm / 3.937 inches
Depth
70.9 mm / 2.791 inches
Depth from upper-edge of DIN-rail
63.7 mm / 2.508 inches

Material Data

Housing material
Polycarbonate; polyamide 6.6
Fire load
2.599 MJ
Weight
167.500 g
Conformity marking
CE

Technical Data

Input voltage (note)
24 VDC (−25 % … +30 %)
Diagnostics
Input voltage failure, fuse triggered
Fuse
Electronic
Power consumption Pmax.
29 W
Data width
2 bits (input voltage failure, fuse triggered)
Intrinsic safety Ex i
Yes
Supply voltage (system)
5 VDC; via data contacts
Current consumption (5 V system supply)
7.5 mA
Supply voltage (field)
24 VDC (-25 … +30 %); (Adjacent Ex i modules are supplied with UO = max. 27.3 V); via power jumper contacts (power supply via CAGE CLAMP® connection; transmission via spring contact)
Power loss Pl
< 5 W
Indicators
LED (A) green: Status voltage supply: Input; LED (B) green/red: Status voltage supply: Output
Number of outgoing power jumper contacts
2
Current carrying capacity (power jumper contacts)
1 A
Marking
ATEX/IECEx: II 3G Ex ec IIC T4 Gc

Mechanical Data

Mounting type
DIN-35 rail

Specifications

Product Group Code
0015

Commercial Data

Packaging type
Box
Country of origin
DE
GTIN
4045454961909
Customs tariff number
85389091890

Notes

Note
General information (e.g., installation regulations) on explosion protection is available in the WAGO I/O System 750 manuals!

Explosion Protection

Ex standard
EN IEC 60079-0, -7, -11
Power supply (output)
Uo = 26.8 V (safe voltage per IEC 60079-11, protection level ia); Un = 24 V ± 0.3 V, In = 1 A
Power supply (input)
Un = 24 VDC (-25 … +30 %); Pmax. = 29 W; Um = 253 V