Insulation type (between adjacent devices of the same type)
Reinforced insulation (safe isolation)
Insulation type (to adjacent devices of different types)
Basic insulation
Protection type
IP20; in connected state or when using 859-525 end plate
Load Circuit
Circuit type
2-wire connection
Limiting continuous current
0.1 A
Output voltage range
DC 3 … 60 V
Voltage drop
≤ 2.5 VDC
Leakage current at rated voltage
≤ 25 µA
Turn-on time
≤ 20 µs
Turn-off time
≤ 120 µs
Switching frequency
≤ 1.5 kHz
Environmental Requirements
Ambient temperature (operation at UN)
-40 … +70 °C
Ambient temperature (storage)
-40 … +70 °C
Processing temperature
-25 … +50 °C
Temperature range of connection cable
≥ (Tambient + 20 K)
Relative humidity
5 … 95 % (no condensation permissible)
Operating altitude (max.)
2000 m
Connection Data
Connection technology
CAGE CLAMP®
Solid conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor
0.08 … 2.5 mm² / 28 … 14 AWG
Fine-stranded conductor; with insulated ferrule
0.08 … 1.5 mm² / 28 … 16 AWG
Strip length
5 … 6 mm / 0.2 … 0.24 inches
Control Circuit
Nominal input voltage UN
DC 5 V
Input voltage range (low level)
DC 0 … 0.8 V
Input voltage range (high level)
DC 2 … 6.25 V
Nominal input current at UN
8 mA
Physical Data
Width
6 mm / 0.236 inches
Height
91 mm / 3.583 inches
Depth from upper-edge of DIN-rail
56 mm / 2.205 inches
Material Data
Color
Gray
Fire load
0.338 MJ
Weight
17.699 g
Standards And Specifications
Standards/specifications
EN 61010-2-201 || EN 61000-6-2 || EN 61000-6-3 || EN 50121-3-2 || EN 61373 || UL 508
Mechanical Data
Mounting type
DIN-35 rail
Mounting position
Horizontal (standing/lying); vertical
Specifications
Product Group Code
0006
Commercial Data
Packaging type
Box
Country of origin
DE
GTIN
4055143606271
Customs tariff number
85365005000
Notes
Note
Optocouplers and solid state relays are designed for use in signal processing networks, which are not supplied by the low-voltage power supply networks.