- Terminal Identifier
- power supply
- Number Of Outputs
- 0
- Height
- 100 mm
- Mounting Support
- 35 mm symmetrical DIN rail
- Minimum Output Voltage
- 5 V relay output
- Response Time
- 60 ms at 48...240 V AC/DC
- Minimum Output Current
- 10 mA relay output
- [Ith] Conventional Free Air Thermal Current
- 6 A
- Associated Fuse Rating
- 10 A gG NO relay output circuit IEC 60947-1
- Local Signalling
- LED green power power ON || LED red error error || LED yellow state status || LED yellow start1 start input || LED yellow start2 start input
- [Uimp] Rated Impulse Withstand Voltage
- 4 kV II IEC 60947-1
- Net Weight
- 0.200 kg
- Type Of Start
- automatic/manual/monitored
- Number Of Inputs
- 0
- Input Compatibility
- normally closed circuit ISO 14119 || XC limit switch ISO 14119 || mechanical contact ISO 14119 || normally closed circuit ISO 13850
- Power Consumption In Va
- 6.0 VA 48...240 V AC 50/60 Hz
- [Ie] Rated Operational Current
- 5 A AC-1 for normally open relay contact || 3 A AC-15 for normally open relay contact || 5 A DC-1 for normally open relay contact || 3 A DC-13 for normally open relay contact || 3 A AC-1 for normally closed relay contact || 1 A AC-15 for normally closed relay contact || 3 A DC-1 for normally closed relay contact || 1 A DC-13 for normally closed relay contact
- Auxiliary Contact Composition
- 4 NO + 1 NC
- [Ui] Rated Insulation Voltage
- 300 V 2)IEC 60947-1
- Power Consumption In W
- 2.0 W 48...240 V DC
- Input Protection Type
- internal, electronic
- Width
- 22.5 mm
- Depth
- 120 mm
- Synchronisation Time Between Inputs
- unlimited