1 / 1
thumbnail

Description

A unique microcontroller-based voltage and phase-sensing circuit constantly monitors the 3-phase voltages to detect harmful power line conditions. When a harmful condition is detected, the output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to acceptable levels. The Model 102A includes advanced single LED diagnostics. Five different light patterns distinguish between faults and normal conditions.
Part Number
102A3
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Input Voltage (V)
190 to 480VAC
Maximum Input Power
5W
Input AC Line Frequency (Hz)
50/60Hz (50Hz will increase all delay timers by 20%.)
Output Form
SPDT - 1 Form C
Output Load Rating (VA)
Pilot Duty: 480VA @ 240VAC; General Purpose: 10A @ 240VAC
Restart Delay Range
After a Fault: 2s; After a Complete Power Loss: 2s
Trip Delay Range
Low/High Voltage: 2-30 seconds adj.; Unbalance and Phasing Faults: 2 seconds
Trip Point Accuracy (%)
±1%
Undervoltage Trip Voltage
90%
Undervoltage Reset Voltage (%)
93%
Voltage Unbalance Trip Point (%)
6%
Voltage Unbalance Reset (%)
4.50%
Termination Type
Torque: 7in-lbs; Wire Size: 12-18AWG
Mounting Method
#8 screws
Operating Temperature
-40° to 70°C (-40° to 158°F)
Storage Temperature (F/C)
-40° to 80°C (-40° to 176°F)
Dimensions
2.93 in H x 5.27 in W x 2.95 in D (74.4 x 133.9 x 74.9 mm)
Weight (lbs/g)
1.05 lbs. (16.8 oz. 476.3 g)