The unique microcontroller-based voltage and voltage-sensing circuit constantly monitors the voltage to detect harmful power line conditions. When a harmful condition is detected, the relay’s output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to an acceptable level and a specified amount of time has elapsed (restart delay). The trip delay prevents nuisance tripping due to rapidly fluctuating power line conditions.- Part Number
- 201-100-SP
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Specifications
- Input Voltage (V)
- 95 to 120VAC
- Maximum Input Power
- 5W
- Input AC Line Frequency (Hz)
- 50/60Hz (50Hz will increase all delay timers by 20%)
- Output Form
- SPDT
- Output Load Rating (VA)
- Pilot Duty: 480VA @ 240VAC; General Purpose: 10A @ 240VAC
- Restart Delay Range
- After a Fault or Complete Power Loss: 2s
- Trip Delay Range
- Under Voltage Fault: 4s
- Undervoltage Trip Voltage
- 90%
- Undervoltage Reset Voltage (%)
- 93%
- Termination Type
- Torque: 12 in-lbs; Wire: Stranded or solid 10-22AWG
- Mounting Method
- DIN rail or surface mount (plug-in to OT08-PC socket)
- Operating Temperature
- -40° to 70°C (-40° to 158°F)
- Storage Temperature (F/C)
- -40° to 80°C (-40° to 176°F)
- Humidity
- 10-95% non-condensing per IEC 68-2-3
- Dimensions
- 1.75 in H x 2.38 in W x 4.13 in D (44.5 x 60.3 x 104.8 mm)
- Weight (lbs/g)
- 0.8 lb. (12.8 oz. 362.87 g)
Documents
Data Sheet
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther