This unique microcontroller-based voltage and phase-sensing device constantly monitors the 3-phase voltages to detect harmful power line conditions. When a harmful condition is detected, the Littelfuse’s output relay is deactivated after a specified trip delay. The output relay reactivates after power line conditions return to acceptable levels. The Model 250A includes advanced single LED diagnostics. Five different light patterns distinguish between faults and normal conditions.
Part Number
250A
$232.46
net
1
Payment methods:
Best offer from:
USTrusted Automa.Net Supplier
Availability:
1 pc.
In-Stock
Updated at: 21-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Specifications

Input Voltage (V)
190 to 480VAC
Maximum Input Power
5W
Input AC Line Frequency (Hz)
50/60Hz (50Hz will increase all delay timers by 20%.)
Output Form
DPDT - 2 Form C
Output Load Rating (VA)
Pilot Duty: 480VA @ 240VAC B300; General Purpose: 10A @ 240VAC
Restart Delay Range
Manual 2 - 300s adjustable
Trip Delay Range
Under/Over Voltage: 4s; Unbalance Phasing Faults: 2s
Trip Point Accuracy (%)
±1%
Overvoltage Trip Voltage (%)
110%
Overvoltage Reset Voltage (%)
107%
Undervoltage Trip Voltage
90%
Undervoltage Reset Voltage (%)
93%
Voltage Unbalance Trip Point (%)
6%
Voltage Unbalance Reset (%)
4.50%
Termination Type
Torque: 7in-lbs; Wire: 12-18AWG
Mounting Method
#8 screws
Operating Temperature
-40° to 70°C (-40° to 158°F)
Humidity
Up to 95% non-condensing per IEC 68-2-3
Dimensions
2.93 in H x 5.27 in W x 2.95 in D (94.4 x 133.9 x 74.9 mm)
Weight (lbs/g)
1.02 lb. (16.3 oz. 462.7 g)

Documents

Data Sheet

Download