Littelfuse

777VA-02

1 / 1
thumbnail

Description

The 777 is a fully programmable electronic overload relay designed to protect any motor drawing 2-800 full load amps (external CTs are required above 90 amps). The 777 (family of products) is for 3-phase 200-480VAC applications, with several specialized units for other voltage ranges and unique applications. Common applications include conveyor systems, HVAC equipment, saws and grinders, fan motors, and almost any pumping application. Some unique applications include use with a Subtrol® equipped Franklin submersible motor to detect high motor temperatures and applications where a fast linear trip is required. All of the overload relays provide unsurpassed protection by combining overload, voltage, phase loss and reversal, voltage and current unbalance, power monitoring, and underload based on current in one package. For standalone applications, the units incorporate a 3-digit LED display that is used for programming, providing real-time operational information and displaying diagnostic codes to aid in troubleshooting a fault condition. The units also feature a communications port that can be used with communication modules listed in the 777 accessories section to form a Modbus, DeviceNet™, Profibus, or Ethernet network. Up to 99 units can be remotely monitored and controlled from a PC, PLC, or SCADA system, and data logging through a PC with the optional Solutions software. This capability allows for a simple, cost-effective way to meet new requirements for arc-flash safety.
Part Number
777VA-02
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Input Voltage (V)
200 to 480VAC
Maximum Input Power
10W
Input AC Line Frequency (Hz)
50/60Hz
Output Form
SPDT - Form C
Output Load Rating (VA)
Pilot Duty: 480VA @ 240VAC B300; General Purpose: 10A @ 240VAC
Full Load Amp Range (A)
2 - 25A (looped conductors required); 25 - 90A (direct); 80 - 800A (external CTs required)
Timing Accuracy (%)
5% ±1s
Rapid Cycle Timer (s)
0 2 - 500m
Restart Delay Range
All faults: 2 - 500m; # of Restarts: All faults except undercurrent: 0 1 oc1 2 oc2 3 oc3 4 oc4 A ocA (Automatic); Undercurrent: 0 1 2 3 4 A (Automatic)
Repeat Accuracy (%)
Voltage: ±0.5% of nominal voltage; Current: ±1% (<100 amps direct)
Overvoltage Trip Voltage (%)
172 - 528V
Undervoltage Trip Voltage
170 - 524V
Voltage Unbalance Trip Point (%)
2 - 15% or 999
Voltage Accuracy (%)
±1%
Overcurrent Trip Point
(20A - 100A) … MULT of 80 - 140% of CT primary
Overcurrent Trip Class
02 - 30 J02 - J30 L00 - L60 or OFF
Undercurrent Trip Point
(0 10 - 98 Amps) … MULT or 40 - 140% of CT primary
Undercurrent Trip Delay (s)
2 - 255m (standard)
Current Unbalance Trip Point (%)
2 - 25% or 999
Current Accuracy (%)
±3% (<100 amps direct)
Ground Fault Current Trip Point (A)
(3 - 20A) … MULT or 12 - 80% of primary CT or OFF
Ground Fault Accuracy (%)
±15%
Sensor Hole Size
Max conductor size: 0.65 in (with insulation)
Short Circuit (kA)
100kA
Surge Protection
IEC: 61000-4-5 Level 3 2kV line-to-line; Level 4 4kV line-to-ground
Protection Class
IP20
Pollution Degree
3
CT Ratio
1 - 10 100 150 200 300 400 500 600 700 800
Address
A01 - A99
Life
Electrical: 1 x 105 operations at rated load; Mechanical: 1 x 106
Termination Type
Torque: 7in-lbs
Mounting Method
Surface mount (4 - #8 screws) on DIN rail mount
Operating Temperature
-20° to 70°C (-4° to 158°F)
Storage Temperature (F/C)
-40° to 80°C (-40° to 176°F)
Humidity
10-95% non-condensing per IEC 68-2-3
Dimensions
3.05 H x 3.85 W x 5.05 D in. (77.5 x 97.8 x 128.3 mm)
Weight (lbs/g)
1.56 lbs. (25.0 oz. 707.6 g)

Documents

Data Sheet

Download