1 / 1
thumbnail

Description

Operation (Delay-on-Make/Delay-on-Break) Forced Air Heating or Air Conditioning (as shown): When the thermostat closes, the compressor relay is immediately energized. At the end of a fixed delay-on-make delay (T1), the fan relay is energized. When the thermostat opens, the compressor relay is de-energized and the delay-on-break delay is initiated. On completion of the fixed delay-on- break delay (T2) the fan relay is de-energized. If the thermostat is reclosed during the delay-on-break delay, the delay-on-break delay is reset and the fan relay remains energized. If the thermostat is closed when input voltage is applied, the delay-on-make delay (T1) begins as normal. Reset: Removing input voltage resets the output and time delays.
Part Number
CT1S8
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Input Voltage (V)
24 VAC
Input Tolerance (%)
±15%
Input AC Line Frequency (Hz)
50/60Hz
Output Type
Solid state
Output Form
NO
Output Load Rating (VA)
0.75A steady state 5A inrush at 55°C
Output Voltage Drop (V)
≅1.25V
Time Delay Type
Microcontroller
Time Delay Range
DOM: 1s; DOB: 8s
Time Delay Tolerance (%)
≤±20%
Recycle Time (ms)
≤300ms
Repeat Accuracy (%)
±5%
Thermostat Anticipator Resistor (Ohms)
Anticipator resistor: ≥3000Ω
Insulation Resistance
≥100 MΩ
Dielectric Breakdown
≥2000V RMS terminals to mounting surface
Circuitry
Encapsulated
Termination Type
0.25 in. (6.35mm) male quick connect terminals
Mounting Method
Surface mount with one #10 (M5 x 0.8) screw
Operating Temperature
-40° to 70°C (-40°F to 158°F)
Storage Temperature (F/C)
-40° to 85°C (-40°F to 185°F)
Humidity
95% relative non-condensing
Dimensions
2.00 x 2.00 x 1.21 in. (50.8 x 50.8 x 30.7mm)
Weight (lbs/g)
≅2.4oz (68g)
Sample capable
No

Documents

Data Sheet

Download