Littelfuse

ISS-105-ISO-F

1 / 1
thumbnail

Description

The ISS-105 has a long list of features that are needed for multiple pump applications. The ISS-105 can indicate low, high and out-of-sequence alarms. If an out-of-sequence alarm occurs, the skipped pump(s) will be started as intended. The Model ISS-105 can be set up to do non-alternating control, alternating control and alternating control with one non-alternating pump. The non-alternating pump is intended for use with an emergency or jockey pump. The ISS-105 can start an emergency pump once every 50 cycles to keep it working freely. Using the built-in DIP switches, individual pumps can be disabled when taken out of service for repair or maintenance.
Part Number
ISS-105-ISO-F
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Input Voltage (V)
120VAC
Input Tolerance (%)
±10%
Maximum Input Power
5W
Input AC Line Frequency (Hz)
50/60Hz (50Hz will increase all delay timers by 20%.)
Input Logic
Input/Output Channels: 5 channels faster response time (≤75s)
Output Load Rating (VA)
Pilot Duty: 480VA @ 240VAC B300; General Purpose: 7A @ 240VAC
Debounce Time Delay (s)
2s
Sense Voltage
5vdc continuous (probe)
Intrinsically Safe Circuit Location
Division 1 and 2; Class I Groups A B C D; Class II Groups E F G; Class III
Protection Class
IP20 (finger safe)
Life
Electrical: 100 000 cycles min. @ rated load; Mechanical: 10 000 000 cycles
Termination Type
Torque: 3.5 to 4.5 in-lbs (max. 6 in.-lbs); Wire: 12-20AWG
Mounting Method
35mm DIN rail or Surface Mount (#6 or #8 screws)
Operating Temperature
-40° to 55°C (-40° to 131°F)
Humidity
10-95% non-condensing per IEC 68-2-3
Dimensions
2.35 in H x 3.70 in W x 5.03 in L (59.7 x 94.1 x 127.6 mm)
Weight (lbs/g)
1.2 lbs. (19.2 oz. 544.31 g)