Operation (Single Shot) Input voltage must be applied before and during timing. Upon momentary or maintained closure of the initiate switch (leading edge triggered), the output energizes for a measured interval of time. At the end of the delay, the output de-energizes. Opening or reclosing the initiate switch during timing has no affect on the time delay. The output will not energize if the initiate switch is closed when input voltage is applied. Reset: Reset occurs when the time delay is complete and the initiate switch is opened. Loss of input voltage resets the time delay and output.
Part Number
KSDS230
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Input Voltage (V)
24VAC
Input Tolerance (%)
±20%
Input AC Line Frequency (Hz)
50/60Hz
Output Type
Solid state
Output Form
NO closed during timing
Output Load Rating (VA)
1A steady state 10A inrush for 16ms
Output Voltage Drop (V)
≅2.5V @ 1A
Time Delay Range
0.1 - 10s onboard adjustable
Time Delay Tolerance (%)
≤±5%
Reset Time (ms)
≤150ms
Initiate Time (ms)
≤20ms
Repeat Accuracy (%)
±0.5% or 20ms whichever is greater
Setpoint vs Ambient Temperature and Operating Voltage (%)
≤ ±10%
Open State Leakage Current (A)
≅5mA @ 230VAC
Insulation Resistance
≥100 MΩ
Dielectric Breakdown
≥2000V RMS terminals to mounting surface
Circuitry
Encapsulated
Power Consumption
≤2VA
Termination Type
0.25 in. (6.35mm) male quick connect terminals
Mounting Method
Surface mount with one #10 (M5 x 0.8) screw
Operating Temperature
-40° to 60°C (-40°F to 140°F)
Humidity
95% relative non-condensing
Dimensions
2.00 x 2.00 x 1.21 in. (50.8 x 50.8 x 30.7mm)
Weight (lbs/g)
≅2.4oz (68g)
Sample capable