Littelfuse

LLC24A2AN

1 / 1
thumbnail

Description

Operation Drain (Pump-Down Mode): When the liquid level rises and touches the high probe, the output relay energizes and remains energized until the liquid level falls below the low probe. The output relay then de-energizes and remains de-energized until the liquid again touches the high probe. Fill (Pump-Up Mode): When the liquid level falls below the low probe, the output relay energizes and remains energized until the liquid level rises and touches the high probe. The output relay then de-energizes and remains de-energized until the liquid level again falls below the low probe.
Part Number
LLC24A2AN
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Input Voltage (V)
120VAC
Input Tolerance (%)
-0.3
Input AC Line Frequency (Hz)
50/60Hz
Output Type
Electromechanical relay
Output Form
Isolated SPDT
Output Load Rating (VA)
10A resistive @ 120/240VAC and 28VDC; 1/3hp @ 120/240VAC
Sense Voltage
12VAC at probe terminals
Sense Resistance (Ohms)
Adjustable to 100kΩ
Sense Resistance Tolerance
Guaranteed range
Control Type
Resistance sensing for high and low level detection of conductive liquids
Isolation Voltage (V)
≥1500V RMS between input output and probe
Circuitry
Printed circuit board is conformal coated to resist moisture and corrosion
Life
Mechanical - 1 x 107; Electrical - 1 x 105
Termination Type
Terminal blocks for up to #14 AWG (2.5mm2) wire
Mounting Method
Surface mount to probe common with two or four #6 (M3.5 x 0.6) screws
Operating Temperature
-20° to 55°C (-4°F to 131°F)
Storage Temperature (F/C)
-40° to 80°C (-40°F to 176°F)
Dimensions
4.00 x 3.00 x 2.00 in. (101.6 x 76.2 x 50.8mm)
Weight (lbs/g)
≅9.0oz (255g)

Documents

Data Sheet

Download