Littelfuse
TL120A5T
1 / 1
Description
Operation (Lockout) Lockout: On initial closure of S1, the compressor relay energizes immediately (or after an optional 1s delay). When the S1 opens or input voltage is interrupted, the output opens and remains open for the lockout time delay. During this lockout time delay period, the compressor relay cannot be re-energized. Reset: The lockout time delay cannot be reset. After the time delay is completed, the unit automatically resets.- Part Number
- TL120A5T
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Specifications
- Input Voltage (V)
- 120VAC
- Input Tolerance (%)
- ±20%
- Input AC Line Frequency (Hz)
- 50/60Hz
- Output Load Rating (VA)
- 0.5A at 60°C
- Minimum Output Load Current (A)
- ≤40mA
- Output Voltage Drop (V)
- ≅4.2V @ 0.5A
- Time Delay Tolerance (%)
- -15% - 35%
- Time Delay Option
- 1s delay-on-make eliminates contactor chatter due to thermostat bounce
- Lockout and Random Start Delays
- 5m fixed
- Initiate Time (ms)
- ≤8ms
- Insulation Resistance
- ≥100 MΩ
- Dielectric Breakdown
- ≥2000V RMS terminals to mounting surface
- Inush
- 10A at 60oC
- Circuitry
- Encapsulated
- Termination Type
- 0.25 in. (6.35mm) male quick connect terminals
- Mounting Method
- Surface mount with one #10 (M5 x 0.8) screw
- Operating Temperature
- -40° to 70°C (-40°F to 158°F)
- Storage Temperature (F/C)
- -40° to 85°C (-40°F to 185°F)
- Humidity
- 95% relative non-condensing
- Dimensions
- 2.00 x 2.00 x 1.21 in. (50.8 x 50.8 x 30.7mm)
- Weight (lbs/g)
- ≅2.4oz (68g)
- Sample capable
- No
Documents
Data Sheet
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther