TVM460A41S5M

1 / 1
thumbnail

Description

Operation Upon application of line voltage, the restart delay begins. The output relay is de-energized during restart delay. Under normal conditions, the output energizes after restart delay. Undervoltage, overvoltage, and voltage unbalance must be sensed for continuous trip delay period before the output is de-energized. The output will not de-energize if a fault is corrected during the trip delay. The restart delay begins as soon as the output relay de-energizes. If the restart delay is completed when the fault is corrected, the output relay will energize immediately. The output relay will not energize if a fault or phase reversal is sensed as 3-phase input voltage is applied. Reset: Reset is automatic upon correction of a fault.
Part Number
TVM460A41S5M
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Input Voltage (V)
460VAC
Input Type
3-phase delta or wye with no connection to neutral
Input AC Line Frequency (Hz)
50-100Hz
Input Phase Sequence
ABC
Output Type
Isolated SPDT relay contacts
Output Load Rating (VA)
10A resistive @ 240VAC; 1/4hp @ 125VAC; 1/3hp @ 250VAC; max voltage 277VAC
Reset Time (ms)
Automatic
Response Time (ms)
Phase loss: ≤200ms; Phase reversal: ≤200ms
Restart Delay Range
5m fixed
Restart Delay Tolerance (%)
±15% or ±0.2s whichever is greater
Trip Delay Range
1s fixed
Trip Delay Tolerance (%)
±15% or ±0.1s whichever is greater
Trip Delay vs Temperature
Trip variation: ≤±2%
Overvoltage Trip Voltage (%)
109 - 113% of the adjusted line voltage
Overvoltage Reset Voltage (%)
≅-3% of the trip voltage
Undervoltage Trip Voltage
88-92% of the adjusted line voltage
Undervoltage Reset Voltage (%)
≅+3% of the trip voltage
Voltage Unbalance Trip Point (%)
4% fixed
Voltage Unbalance Reset (%)
≅-0.7% unbalance
Phase Loss
≥25% unbalance
Power Consumption
≅3W
Dielectric Breakdown
≥2500V RMS input to output terminals
Surge Protection
IEEE C62.41-1991 Level B
Type of Detection
Voltage detection with delayed trip and automatic reset
Life
Mechanical - 1 x 106; Electrical - 1 x 105
Termination Type
0.25 in. (6.35mm) male quick connect terminals
Mounting Method
Suface mount with one #8 (M5 x 0.8) screw
Operating Temperature
-40° to 55°C (-40°F to 131°F)
Storage Temperature (F/C)
-40° to 85°C (-40°F to 185°F)
Humidity
95% relative non-condensing
Dimensions
2.00 x 2.00 x 1.25 in. (50.8 x 50.8 x 31.8mm)
Weight (lbs/g)
≅2.8oz (79g)

Documents

Data Sheet

Download