Description

Mersen HV fuse-links have been used for reliable protection in high-voltage switchgear and controlgear and high-voltage systems for decades. Limitor®-PT HV fuses are back-up fuses as defined in the IEC 60282-1 standard and dedicated to protect transformers against the effects of short-circuit currents. To guarantee high quality, Mersen uses the best materials fuse-elements are in pure silver, caps are in copper coated with silver and bodies are in ceramic.
Country of Origin
FR,HU
Part Number
W1000128
UPC
3605340453010
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

CPD striker
controlled power dissipation
Ampere Rating
40 A
Rated Voltage Ac Iec
12 kV
Ac Max I R Breaking Capacity I1
63 kA
Product Diameter
2.2 in
Ac Min Interrupting Rating Mbc
125 A
Clearing I2T At Rated Voltage
23.3 kA²s
Power Dissipation At Rated Current Value
54 W
Country Of Origin
FR,HU
Product Line
Limitor®- PT Back-up Fuses, with Controlled Power Dissipation
Product Brand
Limitor®
Body Insulating Material
Ceramic
Connection Terminal Material
Silver-Plated Copper
Connection Terminal Type
Cylindrical
Fuse Size
d=56mm, L=292mm
Mounting
Clip