- Rated Operational Voltage
- 208 ... 600 V AC
- Rated Control Supply Voltage (Us)
- 24 V AC/DC
- Rated Control Circuit Voltage (Uc)
- 24 V DC
- Rated Frequency (f)
- 50/60 HzMain Circuit 50 / 60 Hz
- Rated Operational Power - In-Line Connection (Pe)
- (230 V) 3 kW(400 V) 5.5 kW(500 V) 5.5 kW
- Rated Operational Current - In-Line Connection (Ie)
- 12 A
- Service Factor Percentage
- 100 %
- Overload Protection
- Recommended MS132 10.00 ... 16.00
- Integrated Electronic Overload
- No
- Adjustable Rated Motor Current Ie
- No
- Starting Capacity at Maximum Rated Current Ie
- 4xIe for 6s
- Ramp Time
- 0 ... 20 second [unit of time]1 ... 10 second [unit of time]
- Initial Voltage During Start
- 40 ... 70 %
- Step Down Voltage Special Ramp
- 100 ... 60 %
- Current Limit Function
- No
- Switch for Inside Delta Connection
- No
- Run Signal Relay
- Yes
- By-pass Signal Relay
- No
- Fault Signal Relay
- No
- Overload Signal Relay
- No
- Signal Indication Completed Start Ramp (LED)
- Green
- Signal Indication Ready to Start/Standby ON (LED)
- Green
- Signal Indication Running R (LED)
- Green
- Signal Indication Ramping Up/Down (LED)
- Green
- Number of Starts Per Hour at 3.5*Ie for 7 sec. 50% ON Time 50% OFF Time
- 10
- Communication
- FiledBusPlug(Optional)
- Degree of Protection
- IP20
- Terminal Type
- Screw Terminals
- Connecting Capacity Main Circuit
- Rigid 1/2 x 0.75 ... 2.5 mm²
- Connecting Capacity Control Circuit
- 1 x 0.75 ... 2.52 x 0.75 ... 2.5 mm²Rigid 1/2 x 0.75 ... 2.5 mm²
- Connecting Capacity Supply Circuit
- Rigid 1/2 x 0.75 ... 2.5 mm²
- Tightening Torque
- Control Circuit 1 N·mMain Circuit 1 N·mSupply Circuit 1 N·m
- Product Main Type
- PSR12
- Function
- Soft start with voltage rampSoft stop with voltage ramp