ABB

1SFL597025R7011

1 / 1
thumbnail

Description

A 3-pole Contactor suitable for DC-1 applications where all three poles must be connected in series in a 1-pole configuration up to max 1000 VDC. Operated with wide control voltage range 100-250 V, AC/DC
Country of Origin
SE
Part Number
1SFL597025R7011
Tariff Code
85364900
EAN
7320500383971
UNSPSC
39121529
ETIM
Group Code : EG000017
Group Description : Low-voltage Industrial Components
Class Description : Power contactor, DC switching
Class Code : EC002552
Version : 7
Payment methods:
Best offer from:
GBTrusted Automa.Net Supplier
Availability:
100 pcs.
In-Stock
Updated at: 30-04-2024
Estimated Delivery:
On Request
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
A total of 400 Parts In-Stock from 4 Distributors
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Available Offers (3)

1SFL597025R7011 product image
Condition:
New Factory Sealed
Available:
100 pcs.
In-Stock
Updated at: 08-11-2024
Offer from:
GBTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
1SFL597025R7011 product image
Condition:
New Factory Sealed
Available:
100 pcs.
In-Stock
Updated at: 08-11-2024
Offer from:
FRTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
1SFL597025R7011 product image
Condition:
New Factory Sealed
Available:
100 pcs.
In-Stock
Updated at: 18-11-2024
Offer from:
DETrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
Offer with manufacturer lead time
Ships in:On Request
Best price:
€1,047.06

Dimensions

Product Net Width
186 mm
Product Net Depth / Length
216 mm
Product Net Height
278 mm
Product Net Weight
10.6 kg

Technical

Number of Main Contacts NO
1
Number of Main Contacts NC
0
Number of Auxiliary Contacts NO
1
Number of Auxiliary Contacts NC
1
Rated Operational Voltage
Main Circuit 1000 V
Conventional Free-air Thermal Current (Ith)
acc. to IEC 60947-4-1, Open Contactors Θ = 40 °C 700 A
Rated Operational Current DC-1 (Ie)
(1000 V) 3 Poles in Series, 40 °C 700 A(1000 V) 3 Poles in Series, 55 °C 600 A(1000 V) 3 Poles in Series, 70 °C 480 A(220 V) 3 Poles in Series, 40 °C 700 A(220 V) 3 Poles in Series, 55 °C 600 A(220 V) 3 Poles in Series, 70 °C 480 A(400 V) 3 Poles in Series, 40 °C 700 A(400 V) 3 Poles in Series, 55 °C 600 A(400 V) 3 Poles in Series, 70 °C 480 A(600 V) 3 Poles in Series, 40 °C 700 A(600 V) 3 Poles in Series, 55 °C 600 A(600 V) 3 Poles in Series, 70 °C 480 A
Rated Insulation Voltage (Ui)
acc. to UL/CSA 1000 V
Rated Impulse Withstand Voltage (Uimp)
Main Circuit 8 kV
Mechanical Durability
3 million
Maximum Mechanical Switching Frequency
300 cycles per hour
Coil Operating Limits
(acc. to IEC 60947-4-1) 0.85 x Uc Min. ... 1.1 x Uc Max. (at θ ≤ 70 °C)
Rated Control Circuit Voltage (Uc)
50 Hz 100 ... 250 V60 Hz 100 ... 250 VDC Operation 100 ... 250 V
Coil Consumption
Holding at Max. Rated Control Circuit Voltage 50 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage 60 Hz 12 V·AHolding at Max. Rated Control Circuit Voltage DC 4 WPull-in at Max. Rated Control Circuit Voltage 50 Hz 890 V·APull-in at Max. Rated Control Circuit Voltage 60 Hz 890 V·APull-in at Max. Rated Control Circuit Voltage DC 990 V·A
Connecting Capacity Main Circuit
Bar 47 mm²Rigid Al-Cable 2x240 mm²Rigid Cu-Cable 240 mm²
Connecting Capacity Auxiliary Circuit
Flexible with Ferrule 1x 0.75 ... 2.5 mm²Flexible with Insulated Ferrule 2x 0.75 ... 2.5 mm²Flexible 2x0.75 ... 2.5 mm²Solid 2 x 1 ... 4 mm²Stranded 1 x 1 .... 4 mm²
Degree of Protection
acc. to IEC 60529, IEC 60947-1, EN 60529 Coil Terminals IP20acc. to IEC 60529, IEC 60947-1, EN 60529 Main Terminals IP00
Terminal Type
Main Circuit: Bars

Classifications

Object Classification Code
Q
ETIM 4
EC002552 - Power contactor, DC switching
ETIM 5
EC002552 - Power contactor, DC switching
EClass
V11.0 : 27371018
IDEA Granular Category Code (IGCC)
4763 >> Power contactor, DC switching
E-Number (Finland)
3709745

Environmental

Ambient Air Temperature
Operation -40 ... +80 °CStorage -40 ... +70 °C
Maximum Operating Altitude Permissible
Without Derating 3000 m
Resistance to Shock acc. to IEC 60068-2-27
Shock Direction: A 5 gShock Direction: B1 5 gShock Direction: B2 5 gShock Direction: C1 5 gShock Direction: C2 5 g
RoHS Status
Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019

Technical UL/CSA

Maximum Operating Voltage UL/CSA
Main Circuit 600 V
General Use Rating UL/CSA
(1000 V DC) 650 A(440 V DC) 650 A(600 V DC) 650 A

Ordering

Minimum Order Quantity
1 piece
Customs Tariff Number
85364900