ABB
S204M-C10
1 / 4
Description
System pro M compact S200M miniature circuit breakers are current limiting. They have two different tripping mechanisms, the delayed thermal tripping mechanism for overload protection and the electromechanic tripping mechanism for short circuit protection. They are available in different characteristics (B,C,D,K,Z), configurations (1P,1P+N,2P,3P,3P+N,4P), breaking capacities (up to 10 kA at 230/400 V AC) and rated currents (up to 63A). All MCBs of the product range S200M comply with IEC/EN 60898-1 and IEC/EN 609 47-2, allowing the use for residential, commercial and industrial applications. Bottom-fitting auxiliary contact can be mounted on S200M to save 50% space.- Part Number
- S204M-C10
- EAN
- 39121614
- UNSPSC
- 39121603
- ETIM
- Group Code : EG000020
- Group Description : Circuit breakers and fuses
- Class Description : Miniature circuit breaker (MCB)
- Class Code : EC000042
- Version : 7
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 8 pcs.In-StockUpdated at: 18-11-2024
- Estimated Delivery:
- On Request
- Condition:
- New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Installation
- Instructions and Manuals
- 2CDS207104P0002
Dimensions
- Width in Number of Modular Spacings
- 4
- Product Net Width
- 70 mm
- Product Net Height
- 88 mm
- Product Net Depth / Length
- 69 mm
- Product Net Weight
- 0.5 kg
- Pole Net Weight
- 0.125 kg
- Built-In Depth (t2)
- 69 mm
- Dimension Diagram
- 2CDC022007F0010
ABB EcoSolutions
- ABB EcoSolutions
- Yes
Technical
- Standards
- IEC/EN 60898-1CSA 22.2 No. 235IEC/EN 60947-2UL 1077
- Tripping Characteristic
- C
- Rated Operational Voltage
- acc. to IEC 60898-1 400 V ACacc. to IEC 60947-2 440 V AC
- Operational Voltage
- Maximum (Incl. Tolerance) 125 V DCMaximum (Incl. Tolerance) 440 V ACMinimum 12 V ACMinimum 12 V DC
- Rated Insulation Voltage (Ui)
- acc. to IEC/EN 60664-1 440 V
- Rated Impulse Withstand Voltage (Uimp)
- 4 kVat 2000 m 5 kVat Sea Level 6.2 kV
- Dielectric Test Voltage
- 50/60 Hz, 1 min: 2 kV
- Input Voltage Type
- AC/DC
- Rated Current (In)
- 10 A
- Rated Short-Circuit Capacity
- (AC) 10 kA(230 V AC) 10 kA(400 V AC) 10 kA
- Rated Ultimate Short-Circuit Breaking Capacity (Icu)
- (230 V AC) 25 kA(400 V AC) 15 kA(440 V AC) 15 kA
- Rated Conditional Short-Circuit Current (Inc)
- (230 V) 15 kA(400 V) 25 kA
- Rated Service Short-Circuit Breaking Capacity (Ics)
- (230 V AC) 7.5 kA
- Frequency (f)
- 50 Hz
- Rated Frequency (f)
- 50 / 60 Hz
- Power Loss
- 8.4 Wat Rated Operating Conditions per Pole 2.1 W
- Power Supply Connection
- Arbitrary
- Contact Position Indication
- Red ON / Green OFF
- Energy Limiting Class
- 3
- Electrical Endurance
- 20000 AC cycle
- Mechanical Endurance
- 20000 cycle
- Number of Poles
- 4
- Number of Protected Poles
- 4
- Overvoltage Category
- III
- Tightening Torque
- 2.8 N·m
- Screw Terminal Type
- Failsafe Bi-directional Cylinder-lift Terminal
- Actuator Marking
- I / O
- Actuator Material
- Insulation Group II, Black, Sealable
- Housing Material
- Insulation Group II, RAL 7035
- Mounting on DIN Rail
- TH35-15 (35 x 15 mm Mounting Rail) acc. to IEC 60715TH35-7.5 (35 x 7.5 mm Mounting Rail) acc. to IEC 60715
- Mounting Position
- any
- Recommended Screw Driver
- Pozidriv 2
- Accessories Available
- Yes
- Connecting Capacity
- Busbar 10 / 10 mm²Flexible with Ferrule 0.75 ... 25 mm²Flexible 0.75 ... 25 mm²Rigid 0.75 ... 35 mm²Stranded 0.75 ... 35 mm²
- Installation Size
- acc. to DIN 43880 1
- Terminal Type
- Screw Terminals
Eco Transparency
- Environmental Product Declaration - EPD
- 9AKK108467A7833
Classifications
- ETIM 9
- EC000042 - Miniature circuit breaker (MCB)
- EPLAN Function Definition
- Circuit breaker / Quadruple circuit-breaker / Quadruple circuit-breaker 1_2_3_4_5_6_7_8
- WEEE Category
- 5. Small Equipment (No External Dimension More Than 50 cm)
- WEEE B2C / B2B
- Business To Business
- CN8
- 8536 20 10
- EClass
- V11.0 : 27141901
- IDEA Granular Category Code (IGCC)
- 4897 >> Miniature circuit breakers
- Object Classification Code
- F
Environmental
- Ambient Air Temperature
- Operation -25 ... +55 °CStorage -40 ... +70 °C
- Reference Ambient Air Temperature
- 30 °C
- Degree of Protection
- IP20Enclosure with Cover IP40
- Pollution Degree
- 3
- Environmental Conditions
- 28 cycleswith 55 °C / 90-96 %and 25 °C / 95-100 %
- Resistance to Vibrations acc. to IEC 60068-2-6
- 5g, 20 cycles at 5 ... 150 ... 5 Hz with load 0.8 In
- Resistance to Shock acc. to IEC 60068-2-27
- 25g 2 shocks 13 ms
- RoHS Status
- Following EU Directive 2011/65/EU and Amendment 2015/863 July 22, 2019
- RoHS Information
- 2CDK400003K0203
- REACH Declaration
- 9AKK107492A1906
Circular Value
- Circular Design Principles Recyclability Rate
- Design for Closing Resource Loops - Standard EN45555 - 90 %
- Sustainable Material Content
- 0 %
- Offered with Extended Lifetime
- Product Durability
- Offered with Takeback Services
- Take Back for Recycling
Technical UL/CSA
- Maximum Operating Voltage UL/CSA
- 125 V DC480Y/277 V AC
- Interrupting Rating acc. to UL1077
- (125 V DC) 10 kA(277 V AC) 6 kA(480Y / 277 V AC) 6 kA
- Connecting Capacity UL/CSA
- Busbar 14-8 AWGConductor 14-4 AWG
- Tightening Torque UL/CSA
- 18 in·lb
Ordering
- Minimum Order Quantity
- 1 piece
- Package Level 1 Units
- carton 1 piece
- Package Level 1 Gross Weight
- 0.51 kg
- E-Number (Sweden)
- 2101262
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther