Eaton

167114

1 / 2
thumbnail
thumbnail
Part Number
167114
EAN
4015081636167
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Rated operational current for specified heat dissipation (In)
40 A
10.11 Short-circuit rating
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Permitted storage and transport temperature - min
-35 °C
10.4 Clearances and creepage distances
Meets the product standard's requirements.
10.12 Electromagnetic compatibility
Is the panel builder's responsibility. The specifications for the switchgear must be observed.
Mounting Method
Quick attachment with 2 latch positions for DIN-rail IEC/EN 60715
Amperage Rating
40 A
10.2.5 Lifting
Does not apply, since the entire switchgear needs to be evaluated.
Rated fault current - max
.03 A
Test circuit range
184 V AC - 250 V AC, 196 V AC - 305 V AC (UL)
10.2.3.1 Verification of thermal stability of enclosures
Meets the product standard's requirements.
Tripping time
Non-delayed
Fitted with:
Interlocking device
Rated residual making and breaking capacity
500 A
Frequency rating
50 Hz / 60 Hz
10.8 Connections for external conductors
Is the panel builder's responsibility.
Fault current rating
30 mA
Terminal protection
Busbar tag shroud to BGV A3, ÖVE-EN 6
Special features
Current test marks as per inscription\nMaximum operating temperature is 75 °C: Starting at 40 °C, the max. permissible continuous current decreases by 2.5% for every 1 °C\nThe maximum operating current of back-up fuse must not exceed the residual current circuit breaker's rated operational current
Sensitivity type
Pulse-current sensitive
Ambient operating temperature - max
40 °C
Heat dissipation per pole, current-dependent
3.9 W
Climatic proofing
25-55 °C / 90-95% relative humidity according to IEC 60068-2
Built-in depth
70.5 mm
Short-circuit rating
Max. admissible back-up fuse: 63 A gG/gL, 70 A class J fuse (UL)
Features
Additional equipment possible
Lifespan, electrical
4000 operations
Terminal capacity (cable)
M5 (with cross-recessed screw as defined in EN ISO 4757-Z2, PZ2)
Connectable conductor cross section (solid-core) - min
1.5 mm²
Contact position indicator color
Red / green
10.9.3 Impulse withstand voltage
Is the panel builder's responsibility.
Number of poles
Two-pole
Terminal capacity (solid wire)
1.5 mm² - 35 mm²
Ambient operating temperature - min
-25 °C
10.6 Incorporation of switching devices and components
Does not apply, since the entire switchgear needs to be evaluated.
Rated short-circuit strength
10 kA with back-up fuse
10.5 Protection against electric shock
Does not apply, since the entire switchgear needs to be evaluated.
Mounting position
As required
Equipment heat dissipation, current-dependent
7.8 W
10.13 Mechanical function
The device meets the requirements, provided the information in the instruction leaflet (IL) is observed.
10.2.6 Mechanical impact
Does not apply, since the entire switchgear needs to be evaluated.
10.9.4 Testing of enclosures made of insulating material
Is the panel builder's responsibility.
Static heat dissipation, non-current-dependent
0 W
Application
Switchgear for export to North America (UL-listed)
10.3 Degree of protection of assemblies
Does not apply, since the entire switchgear needs to be evaluated.
Voltage rating (IEC/EN 60947-2)
240 V AC / 415 V AC
Terminal capacity (stranded cable)
16 mm² (2x)
Leakage current type
A
Frame
45 mm
Built-in width (number of units)
35 mm (2 SU)
Terminals (top and bottom)
Lift terminals
Heat dissipation capacity
0 W
Ambient humdity range
5 - 95 %
Impulse withstand current
250 A (8/20 μs) surge-proof
Width in number of modular spacings
2
10.2.3.2 Verification of resistance of insulating materials to normal heat
Meets the product standard's requirements.
10.2.3.3 Resist. of insul. mat. to abnormal heat/fire by internal elect. effects
Meets the product standard's requirements.
Lifespan, mechanical
10000 operations
Status indication
White / blue
10.9.2 Power-frequency electric strength
Is the panel builder's responsibility.
Connectable conductor cross section (solid-core) - max
35 mm²
Degree of protection
IP20, IP40 with suitable enclosure
Rated short-time withstand current (Icw)
10 kA
Overvoltage tested - max
530 V
Pollution degree
2
10.7 Internal electrical circuits and connections
Is the panel builder's responsibility.
Connectable conductor cross section (multi-wired) - min
1.5 mm²
Rated impulse withstand voltage (Uimp)
4 kV (1.2/50 µs)
10.10 Temperature rise
The panel builder is responsible for the temperature rise calculation. Eaton will provide heat dissipation data for the devices.
Voltage rating (UL)
480Y/277 V, 60 Hz
Connectable conductor cross section (multi-wired) - max
16 mm²
Type
FRCmM-NA\nResidual current circuit breakers\nType A
10.2.2 Corrosion resistance
Meets the product standard's requirements.
10.2.4 Resistance to ultra-violet (UV) radiation
Meets the product standard's requirements.
10.2.7 Inscriptions
Meets the product standard's requirements.
Surge current capacity
.25 kA
Permitted storage and transport temperature - max
60 °C
Admissible back-up fuse overload - max
40 A gG/gL
Rated fault current - min
.03 A
Pick-up current
22 mA
Rated operational voltage (Ue) - max
277 V
Rated insulation voltage (Ui)
440 V

General

Model Code
FRCMM-40/2/003-A-NA
EAN
4015081636167
Product Length/Depth
80 mm
Product Height
71 mm
Product Width
35 mm
Product Weight
.22 kg
Compliances
RoHS conform
Certifications
UL 1053
Catalog Notes
Protects against special forms of residual pulsating DC which have not been smoothed.