Littelfuse

201-100-DPDT-60MS

1 / 1
thumbnail

Description

The unique microcontroller-based voltage and phase-sensing circuit constantly monitors the voltages to detect harmful power line conditions. When a harmful condition is detected, the relay’s output relays are deactivated after a specified trip delay. The output relays reactivate after power line conditions return to an acceptable level and a specified amount of time has elapsed (restart delay). The trip delay prevents nuisance tripping due to rapidly fluctuating power line conditions. This unit is also available with a shorter trip delay and faster restart delay. The 201-xxx-DPDT-60mS has a trip delay of 0.5 seconds and a restart delay of 60 milliseconds.
Part Number
201-100-DPDT-60MS
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Specifications

Input Voltage (V)
95 to 120VAC
Maximum Input Power
5W
Input AC Line Frequency (Hz)
50/60Hz
Output Form
DPDT
Output Load Rating (VA)
Pilot Duty: 480VA @ 240VAC; General Purpose: 10A @ 240VAC
Restart Delay Range
After a Fault or Complete Power Loss: 60ms
Trip Delay Range
Low Voltage: 0.5s; Unbalance Phasing Faults: 0.5s
Trip Point Accuracy (%)
±1%
Undervoltage Trip Voltage
90%
Undervoltage Reset Voltage (%)
93%
Voltage Unbalance Trip Point (%)
6%
Voltage Unbalance Reset (%)
4.50%
Termination Type
Torque: 12 in-lbs; Wire: Stranded or solid 10-22AWG
Mounting Method
DIN rail or surface mount (plug-in to OT11-PC socket)
Operating Temperature
-40° to 70°C (-40° to 158°F)
Humidity
95% non-condensing per IEC 68-2-3
Dimensions
1.75 in H x 2.38 in W x 4.13 in D (44.5 x 60.3 x 104.8 mm)
Weight (lbs/g)
0.65 lb. (10.4 oz. 294.8 g)

Documents

Data Sheet

Download