TeSys F magnetic latching contactor, 3 poles (3NO), 400A/1000V AC-3, for motor applications up to 200kW@400V. It provides a double coil 110V AC (50-400Hz) or DC for latching and unlatching, bolt terminals for bars or cables with lugs. Supply to the coils must be applied by pulsed contacts leading to energy saving and no sensibility to interferences for contactors remaining in closed state for long periods. For operating rates until 120 cycles/hour and environments until 70°C, it procures high reliability and durability. It makes installation and maintenance easy thanks to its drawer-mounted coil and a large choice of add-on blocks (instantaneous and time delay auxiliary contacts, suppressor blocks) and connection accessories (to be ordered separately). It conforms to IEC 60158-1 and IEC 60947-4, Green Premium product (RoHS/REACh).
Country of Origin
CZ
Part Number
CR1F400F7
Tariff Code
85364190
EAN
3389110548532
UNSPSC
39121529
Payment methods:
Best offer from:
DETrusted Automa.Net Supplier
Availability:
1 pc.
In-Stock
Updated at: 22-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Environment

Ambient Air Temperature For Operation
-15-70 °C
Height
206 mm
Net Weight
9.1 kg
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TC
Operating Altitude
9842.52 ft (3000 m) without derating
Width
213 mm
Depth
219 mm

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1505009EN
Sustainable Offer Status
Green Premium product
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI1505009EN
Eu Rohs Directive
Compliant with Exemptions

Complementary

Control Circuit Voltage Limits
latching: 0.85...1.1 Uc || unlatching: 0.85...1.1 Uc
Average Coil Consumption
1600 VA AC 50...400 Hz latching || 16 VA AC 50...400 Hz unlatching || 1600 VA DC latching || 16 VA DC unlatching

Specifications

Product Certifications
CB Scheme || UL || CSA || EAC || CE || UKCA
[Ue] Rated Operational Voltage
1000 V AC 25...200 Hz
Power Dissipation Per Pole
45 W AC-3 || 70 W AC-1
Average Impedance
0.28 mOhm - Ith 500 A 50 Hz
Standards
EN/IEC 60947-1 || EN/IEC 60947-4-1 || JIS C8201-4-1 || UL 60947-4-1 || CSA C22.2 No 60947-4-1
Control Circuit Type
AC 50...400 Hz || DC standard
[Uc] Control Circuit Voltage
110 V AC 50...400 Hz || 110 V DC
Contactor Application
resistive load || motor control
Rated Breaking Capacity
4000 A at 220...440 V || 3500 A at 500 V || 1200 A at 1000 V || 3000 A at 660/690 V
Product Or Component Type
magnetic latching contactor
Irms Rated Making Capacity
4500 A
Product Name
TeSys F
Associated Fuse Rating
400 A aM at <= 440 V || 500 A BS88 at <= 440 V || 500 A gG at <= 440 V
Connections - Terminals
lugs-ring terminals 2 150-150 mm² || bars 2 30 x 5 mm || power circuit bolted connection
Range
TeSys
Pole Contact Composition
3 NO
Utilisation Category
AC-1 || AC-3 || AC-4
[Ie] Rated Operational Current
400 A (at <40 °C) at <= 440 V AC AC-3 || 500 A (at <40 °C) at <= 440 V AC AC-1 || 370 A (at <40 °C) at <= 440 V AC AC-4
Maximum Operating Rate
120 cyc/h 40 °C
Tightening Torque
35 N.m
Mechanical Durability
1 Mcycles
Poles Description
3P
Operating Time
40...75 ms latching || 50...100 ms unlatching
Motor Power Kw
200 kW at 400 V AC 50/60 Hz (AC-4)
[Ui] Rated Insulation Voltage
1000 V IEC 60158-1 || 1000 V IEC 60947-4 || 1000 V BS 775 || 1500 V VDE 0110 group C
Device Application
control
Device Short Name
CR1F
[Icw] Rated Short-Time Withstand Current
3600 A 40 °C - 1 s || 3600 A 40 °C - 5 s || 3600 A 40 °C - 10 s || 2400 A 40 °C - 30 s || 1700 A 40 °C - 1 min || 1200 A 40 °C - 3 min || 1000 A 40 °C - 10 min