- Line Rated Current
- 23 A
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz IEC 60947-2
- Height
- 101 mm
- Phase Failure Sensitivity
- yes IEC 60947-4-1
- Rated Duty
- continuous IEC 60947-4-1
- Network Type
- AC
- Magnetic Tripping Current
- 327-327 A
- [Ith] Conventional Free Air Thermal Current
- 23 A IEC 60947-4-1
- Motor Power Kw
- 9-9 kW 400/415 V AC 50/60 Hz || 11-11 kW 400/415 V AC 50/60 Hz || 11-11 kW 500 V AC 50/60 Hz
- Utilisation Category
- category A IEC 60947-2 || AC-3 IEC 60947-4-1 || AC-3e IEC 60947-4-1
- Net Weight
- 0.28 kg
- Fixing Mode
- 35 mm symmetrical DIN rail clipped || panel screwed with adaptor plate)
- [Uimp] Rated Impulse Withstand Voltage
- 6 kV IEC 60947-2
- [Ics] Rated Service Short-Circuit Breaking Capacity
- 100 % 230/240 V AC 50/60 Hz IEC 60947-2 || 40 % 400/415 V AC 50/60 Hz IEC 60947-2 || 50 % 440 V AC 50/60 Hz IEC 60947-2 || 75 % 500 V AC 50/60 Hz IEC 60947-2 || 75 % 690 V AC 50/60 Hz IEC 60947-2
- Control Type
- push-button
- Power Dissipation Per Pole
- 2.5 W
- Electrical Durability
- 100000 cycles AC-3 415 V In || 100000 cycles AC-3e 415 V In
- [Ui] Rated Insulation Voltage
- 690 V AC 50/60 Hz IEC 60947-2
- Breaking Capacity
- 50 kA Icu 230/240 V AC 50/60 Hz IEC 60947-2 || 15 kA Icu 400/415 V AC 50/60 Hz IEC 60947-2 || 6 kA Icu 440 V AC 50/60 Hz IEC 60947-2 || 4 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 3 kA Icu 690 V AC 50/60 Hz IEC 60947-2
- Suitability For Isolation
- yes IEC 60947-1 § 7-1-6
- Thermal Protection Adjustment Range
- 17-23 A IEC 60947-4-1
- Mechanical Durability
- 100000 cycles
- Poles Description
- 3P
- Color
- dark grey
- Width
- 45 mm
- Depth
- 78.5 mm
- Network Frequency
- 50/60 Hz IEC 60947-4-1