The MN undervoltage release is designed for use with TeSys GV2 and GV3 motor circuit breakers. It operates within a control voltage range of 110-115V AC at 50Hz and 127V AC at 60Hz. This device triggers a trip when the control voltage falls below 0.35 times the nominal voltage, with the potential to open the circuit between 0.35 and 0.7 times the nominal voltage. Circuit closure is permissible only when applying a control voltage between 0.85 and 1.1 times the nominal voltage.
Installation is facilitated on the right-hand side of the circuit breaker, utilizing screw clamp terminals for connections. The unit has a net weight of 0.105 kg and dimensions of 89 mm in height, 18 mm in width, and 66 mm in depth. It consumes 1.1W of hold-in power and has a mechanical durability rating of 30,000 cycles with compatible units like GV2ME and GV2P. The inrush power is rated at 12VA AC.
This product meets multiple international standards, including IEC, UL, CSA, and CCC, and is compliant with Green Premium standards, ensuring it is free from substances of very high concern as per REACh regulations.