1 / 1
thumbnail

Description

Active Mature
TeSys GV electrical trip, MX shunt release, 110-115V AC 60Hz, for motor circuit breakers GV2, GV3. It trips the circuit breaker when the control voltage is applied in limits 0.7-1.1 Uc with an impulse duration greater than 20ms or a maintained signal. To be mounted on right-hand side of the circuit breaker, connection by screw clamp terminals. Multi standards certified (IEC, UL, CSA, CCC, EAC), Green Premium compliant (RoHS/REACh).
Country of Origin
CZ
Part Number
GVAS116
Tariff Code
85363090
EAN
3389110343694
UNSPSC
39121521
Payment methods:
Best offer from:
GBTrusted Automa.Net Supplier
Availability:
5 pcs.
In-Stock
Updated at: 21-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2207006
Sustainable Offer Status
Green Premium product
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
ENVEOLI2207006
Eu Rohs Directive
Compliant

Specifications

Product Or Component Type
shunt trip release
Range
TeSys || TeSys Deca
Device Short Name
GVAS

Complementary

[Uc] Control Circuit Voltage
110...115 V AC 60 Hz
Control Circuit Voltage Limits
0.7...1.1 Un
Height
89 mm
Tightening Torque
< 1.4 N.m screw clamp terminals
Range Compatibility
TeSys GV2ME || TeSys GV2LE || TeSys GV2L || TeSys GV2P || TeSys GV3L || TeSys GV3P || TeSys Deca
Hold-In Power Consumption In W
1.6-1.6 W
Net Weight
0.105 kg
Inrush Power In Va
14-14 VA AC
Connections - Terminals
screw clamp terminals 1 1-2.5 mm²solid || screw clamp terminals 2 1-2.5 mm²solid || screw clamp terminals 1 0.75-2.5 mm²flexible without cable end || screw clamp terminals 2 0.75-2.5 mm²flexible without cable end || screw clamp terminals 1 0.75-1.5 mm²flexible with cable end || screw clamp terminals 2 0.75-1.5 mm²flexible with cable end
[Ui] Rated Insulation Voltage
690 V AC IEC 60947-1 || 600 V AC UL 60947-4-1 || 600 V AC CSA C22.2 No 60947-4-1
Mechanical Durability
10000 cycles with GV3P and GV3L || 30000 cycles with GV2ME and GV2P
Threshold Tripping Voltage
0.75...0.2 Un
Hold-In Power Consumption In Va
5-5 VA AC
On-Load Factor
100 %
Quantity Per Set
set of 10
Operating Time
10...15 ms IEC 60947-1
Color
dark grey
Width
18 mm
Depth
66 mm
Inrush Power In W
10.5 W

Contractual warranty

Warranty
18 months

CAD Models

traceparts
traceparts
Download