1 / 1
thumbnail

Beschreibung

Aktiv Reif
TeSys Deca mechanical latch block, for LC1D09-D80A, LC1DT20-DT80A contactors and CAD control relays (except devices with low consumption coils). Electrical latching and unlatching is performed applying a 256-277V control voltage pulse (> 100ms in AC, 250ms in DC). Unlatching can be manually operated. Clip-on mounting on front of contactor, connection by screw terminals. For applications with high operating rates until 1200 cycles/hour. Multi standards certified (IEC, UL, CSA), Green Premium compliant (RoHS/REACh).
Country of Origin
FR
Part Number
LAD6K10U
Tariff Code
85389099
EAN
3389110842456
UNSPSC
39122317
Zahlungsmethoden:
Bestes Angebot von:
DEVertrauenswürdiger Automa.Net Lieferant
Verfügbarkeit:
1 Stk.
Auf Lager
Aktualisiert am: 04-11-2024
Garantie:
12 Monate
Geschätzte Lieferung:
Auf Anfrage
Zustand:
Neuer Überschuss
Neuer Überschuss - Ein neuer, unbenutzter, unbeschädigter Artikel ohne Herstellergarantie. Der Artikel kann ohne Originalverpackung oder in Ersatzverpackung geliefert werden. Wenn vorhanden, könnte die Verpackung geöffnet worden sein.
Sicherer Zahlungsprozess
Rückgabe- und Erstattungsrichtlinien
Versandrichtlinien
Garantiebedingungen

Environment

Product Certifications
CSA || UL
Ambient Air Temperature For Operation
-25-55 °C
Ip Degree Of Protection
IP2XVDE 0106
Ambient Air Temperature For Storage
-40-80 °C
Protective Treatment
THIEC 60068

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP2011001
Sustainable Offer Status
Green Premium product
Toxic Heavy Metal Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI2011001
Eu Rohs Directive
Compliant with Exemptions

Complementary

Power Required In W
30 W DC
Tripping Control
manual || electrical
Net Weight
0.07 kg
Mounting Location
front side
[Ui] Rated Insulation Voltage
690 V IEC 60947-5-1
Maximum Operating Rate
1200 cyc/h
Mechanical Durability
500000 cycles
On-Load Factor
10 %
Power Required In Va
25 AC

Specifications

[Uc] Control Circuit Voltage
256/277 V AC 50/60 Hz || 256/277 V DC
Product Compatibility
LC1D09...D38 AC/DC || LC1DT20...DT40 AC/DC || LC1D40A...D80A 3 phase AC/DC || LC1DT60A 3 phases + neutral AC/DC || LC1DT80A 3 phases + neutral AC/DC
Product Or Component Type
mechanical latch block
Range
TeSys

CAD Models

traceparts
traceparts
Herunterladen