Schneider Electric
LR9F5357
1 / 1
Description
Active Mature
TeSys LR9F electronic overload relay, thermal setting range 30-50A, class 10, for protection of motors 18.5-22kW@400V. to be mounted directly below a TeSys F 3-pole contactor LC1 F115, F150, F185, use of a support mounting plate LA7F901 is recommended (to be ordered separately). Motor protection includes thermal overload of 1-phase and 3-phase motors, phase failure, phase unbalance, prolonged starting times, stalled rotor conditions. On the front of the relay, it provides a thermal adjustement dial, buttons for test, stop & reset, a trip indicator, trip auxiliary contacts 1NO+1NC. Multi standards certified (IEC, UL, CSA, CCC, Marine), Green Premium compliant (RoHs/Reach).- Country of Origin
- FR
- Part Number
- LR9F5357
- Tariff Code
- 85364900
- EAN
- 3389110565973
- UNSPSC
- 39122330
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 1 pc.In-StockUpdated at: 21-11-2024
- Warranty:
- 12 months
- Estimated Delivery:
- On Request
- Condition:
- New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Specifications
- Network Type
- AC
- Thermal Protection Adjustment Range
- 30-50 A
- Relay Application
- motor protection
- Product Or Component Type
- electronic thermal overload relay
- Product Name
- TeSys LRF
- Thermal Overload Class
- class 10 IEC 60947-4
- Range
- TeSys
- Product Compatibility
- LC1F115...LC1F185
- Device Short Name
- LR9F
Contractual warranty
- Warranty
- 18 months
Complementary
- Network Frequency
- 50/60 Hz
- Current Consumption
- <= 5 mA no-load
- Height
- 96 mm
- [Ith] Conventional Free Air Thermal Current
- 5 A control circuit
- Tightening Torque
- control circuit 1.2 N.m screw clamp terminals || power circuit 10 N.m screw clamp terminals
- Reset
- manual reset on front relay
- Phase Failure Sensitivity
- tripping in 4 s +/- 20 % IEC 60947-4-1
- [Ue] Rated Operational Voltage
- 1000 V AC 50/60 Hz power circuit VDE 0110 group C
- Switching Capacity In Ma
- 0...150 mA
- Net Weight
- 0.885 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947-1
- Maximum Voltage Drop
- <2.5 V closed state
- Connections - Terminals
- control circuit screw clamp terminals 1 0.75-2.5 mm² flexible - with cable end || control circuit screw clamp terminals 1 0.75-2.5 mm² solid || control circuit screw clamp terminals 1 0.75-4 mm² flexible - without cable end || control circuit screw clamp terminals 2 1-1.5 mm² flexible - with cable end || control circuit screw clamp terminals 2 1-2.5 mm² flexible - without cable end || control circuit screw clamp terminals 2 1-1 mm² solid || power circuit lugs-ring terminals M6
- [Ui] Rated Insulation Voltage
- power circuit 1000 V AC IEC 60947-4
- Contacts Type And Composition
- 1 NO + 1 NC
- Surge Withstand
- 4 kV IEC 61000-4-5
- Tripping Threshold
- 1.12 +/- 0.06 In tripping IEC 60947-4-1
- Mounting Support
- direct on contactor || plate
- Control Type
- dial White full-load current adjustment || test button Red || push-button Red reset || push-button stop
- Local Signalling
- trip indicator
- Width
- 115 mm
- Depth
- 123.5 mm
- Temperature Compensation
- -20-70 °C
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP080207EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Product out of China RoHS scope. Substance declaration for your information.
- Circularity Profile
- ENVEOLI100406
- Eu Rohs Directive
- Compliant
Environment
- Product Certifications
- CSA || UL || UKCA
- Mechanical Robustness
- shocks13 Gn for 11 ms IEC 60068-2-7 || vibrations 5...300 Hz2 GN IEC 60068-2-6
- Standards
- IEC 60255-8 || IEC 60947-4-1 || VDE 0660 || IEC 60255-17 || EN 60947-4-1
- Ambient Air Temperature For Operation
- -20-55 °C IEC 60255-8
- Electromagnetic Compatibility
- resistance to electrostatic discharge 6 kV in indirect mode IEC 61000-4-2 || resistance to electrostatic discharge 8 kV in air IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test 10 V/m IEC 61000-4-3 || fast transients immunity test 2 kV IEC 61000-4-4
- Dielectric Strength
- 6 kV 50 Hz IEC 255-5
- Ip Degree Of Protection
- IP20 conforming to IEC 60529 || IP20 conforming to VDE 0106
- Ambient Air Temperature For Storage
- -40-85 °C
- Protective Treatment
- TH
- Operating Altitude
- <= 6561.68 ft (2000 m) without derating
- Fire Resistance
- 850 °C IEC 60695-2-1
CAD Models
traceparts
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther