This Compact NSX250HB1 is a complete 3P 3d fixed circuit breaker designed to optimize space and breaking capacity. It is an optimal choice for all standard and specific applications. The breaking capacity (Icu) is 85kA rms at 500VAC 50/60Hz and 75kA rms at 690VAC 50/60Hz. The operational voltage is 690VAC 50/60Hz. This product embeds a 160A rating electronic Micrologic 6.2 E trip unit, with an adjustable ground-fault protection (with OFF position). Micrologic 6.2 E trip unit provides adjustable long time, short time and instantaneous protection. Micrologic 6.2 E has an embedded display unit for fine settings adjustment and display of the energy (energy meter). This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. It is compliant with international standards (IEC 60947), CCC, EAC and marine specifications. Compact NSX250HB1 is part of Schneider Electric EcoStruxure Power architecture.
Country of Origin
FR
Part Number
LV433556
Tariff Code
85362090
EAN
3606480480492
UNSPSC
39121601
Payment methods:
Best offer from:
DETrusted Automa.Net Supplier
Availability:
1 pc.
In-Stock
Updated at: 08-11-2024
Warranty:
12 months
Estimated Delivery:
On Request
Condition:
New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Specifications

Network Frequency
50/60 Hz
Line Rated Current
160 A 40 °C
Trip Unit Name
MicroLogic 6.2 E
Range Of Product
ComPact NSX100...250
[Ue] Rated Operational Voltage
690 V AC 50/60 Hz
Trip Unit Protection Functions
LSIG
Network Type
AC
Protected Poles Description
3t
Product Or Component Type
circuit breaker
Product Name
ComPact NSX
Range
ComPact
Control Type
toggle
Utilisation Category
category A
Mounting Mode
fixed
Breaking Capacity
85 kA Icu 500 V AC 50/60 Hz IEC 60947-2 || 80 kA Icu 525 V AC 50/60 Hz IEC 60947-2 || 75 kA Icu 660/690 V AC 50/60 Hz IEC 60947-2
Suitability For Isolation
yes EN/IEC 60947-2
Poles Description
3P
Breaking Capacity Code
HB1 75 kA 690 V AC
Device Application
distribution
Device Short Name
NSX250HB1
Trip Unit Technology
electronic

Contractual warranty

Warranty
18 months

Complementary

[Tg] Ground-Fault Time Delay Adjustment Range
0-0.4 s I²t=off || 0.1-0.4 s I²t=on
[Ics] Rated Service Breaking Capacity
85 kA 500 V AC 50/60 Hz IEC 60947-2 || 80 kA 525 V AC 50/60 Hz IEC 60947-2 || 75 kA 660/690 V AC 50/60 Hz IEC 60947-2
Height
161 mm
[Ig] Ground-Fault Pick-Up Adjustment Range
0.2...1 x In || Ig enable on/off
Thermal Memory
20 minutes before and after tripping
Earth-Leakage Protection
without
Ground-Fault Time Delay Adjustment Type -Tg
adjustable 5 settings
Mounting Support
backplate
Ground-Fault Pick-Up Adjustment Type
adjustable 9 settings
Instantaneous Pick-Up Adjustment Range
1.5...15 x In
Type Of Measurement
energy meter
Downside Connection
front
Number Of Slots
5
Communication Of Data
protection and alarm settings || maximeters/minimeters || demand current and power || power quality || time-stamped histories and event tables || energy metering || instantaneous and demand values || maintenance indicators
Protection Type
L : for overload protection (long time) || S : for short time short-circuit protection || I : for instantaneous short-circuit protection || G : for ground fault protection
Long Time Delay Adjustment Type
adjustable
Instantaneous Pick-Up Adjustment Type Ii
adjustable
Zone Selective Interlocking Zsi
with
Net Weight
2.4 kg
[Tr] Long-Time Delay Adjustment Range
15-400 s 1.5 x Ir || 0.35-11 s 7.2 x Ir || 0.5-16 s 6 x Ir
Electrical Durability
5000 cycles 690 V In || 10000 cycles 690 V In/2 || 10000 cycles 440 V In || 20000 cycles 440 V In/2
Short-Time Delay Adjustment Type
adjustable 5 settings
Long Time Pick-Up Adjustment Type Ir
adjustable 9 settings
Long Time Pick-Up Adjustment Range
63...160 A
Upside Connection
front
[Tsd] Short-Time Delay Adjustment Range
0-0.4 s
[Ui] Rated Insulation Voltage
800 V AC 50/60 Hz
Trip Unit Rating
160-160 A 40 °C
Local Signalling
for ready to operate flashing LED (green) || for overload LED 105 % Ir (red) || for overload LED 90 % Ir (orange)
Mechanical Durability
20000 cycles
[Isd] Short-Time Pick-Up Adjustment Range
1.5...15 x In
Connection Pitch
35 mm
[Uimp] Rated Impulse Withstand Voltage
8 kV
Width
105 mm
Display Type
LCD display
Depth
86 mm
Short-Time Pick-Up Adjustment Type Isd
adjustable

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP120606EN
Sustainable Offer Status
Green Premium product
California Proposition 65
WARNING: This product can expose you to chemicals including: DINP, which is known to the State of California to cause cancer, and DIDP, which is known to the State of California to cause birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI120604EN
Eu Rohs Directive
Compliant

Environment

Product Certifications
EAC || Marine || CCC
Ik Degree Of Protection
IK07 IEC 62262
Ambient Air Temperature For Operation
-25-70 °C
Standards
EN/IEC 60947
Ip Degree Of Protection
IP40 conforming to IEC 60529
Electrical Shock Protection Class
class II
Pollution Degree
3 IEC 60664-1
Ambient Air Temperature For Storage
-40-85 °C
Relative Humidity
0-95 %
Operating Altitude
0...6561.68 ft (0...2000 m) without derating || 2000 m...5000 m with derating
Overvoltage Category
class II