Schneider Electric
RM17TA00
1 / 5
Description
Active Mature
This Harmony RM17-TA relay allows monitoring of power supply circuits in 3-phase networks. This modular multi function 3-phase supply control relay is ideal for monitoring of electrical values in industrial and building control panels. It applies to a wide type of industrial automation applications such as hoisting, packaging, lifts, textile, water. It has one of market slimmest form-factors with 17.5mm width, allowing for a flexible and easy installation on DIN rail, using the same space as any modular 1-pole DIN device. It also offers a sealable cover, simple and precise settings with screw trimmers. The product monitors its own power supply, when the power supply is abnormal, the output relay de-energizes. multi function controller for wide choice selected in hard-wired logic automated systems, ideal for refurbishment of old installations without using a PLC. 0 0 0 0 0 0 0 0 0 0 0 0- Country of Origin
- ID
- Part Number
- RM17TA00
- Tariff Code
- 85364900
- EAN
- 3389119405041
- UNSPSC
- 39122331
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 10 pcs.In-StockUpdated at: 22-11-2024
- Warranty:
- 12 months
- Estimated Delivery:
- On Request
- Condition:
- New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Environment
- Product Certifications
- GOST || CSA || GL || C-tick || UL
- Standards
- IEC 60255-1
- Non-Dissipating Shock Wave
- 4 kV IEC 60255-5 || 4 kV IEC 60664-1 || 4 kV IEC 61000-4-5
- Dielectric Test Voltage
- 2 kV AC 50 Hz, 1 min IEC 60255-5 || 2 kV AC 50 Hz, 1 min IEC 60664-1
- Electromagnetic Compatibility
- emission standard for industrial environments conforming to IEC 61000-6-4 || emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3 || immunity for industrial environments conforming to IEC 61000-6-2
- Shock Resistance
- 15 gn 11 ms IEC 60255-21-1
- Ambient Air Temperature For Operation
- -20-50 °C
- Vibration Resistance
- 0.35 mm 5-57.6 Hz)IEC 60068-2-6 || 1 gn 57.6-150 Hz)IEC 60255-21-1
- Ip Degree Of Protection
- IP20 IEC 60529 terminals) || IP30 IEC 60529 casing)
- Pollution Degree
- 3 IEC 60664-1
- Directives
- 89/336/EEC - electromagnetic compatibility || 73/23/EEC - low voltage directive
- Ambient Air Temperature For Storage
- -40-70 °C
- Relative Humidity
- 95-95 % 55-55 °C IEC 60068-2-30
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP1504008EN
- Sustainable Offer Status
- Green Premium product
- Reach Regulation
- Reference contains Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
- China Rohs Regulation
- X
- Circularity Profile
- ENVEOLI1504008EN
- Eu Rohs Directive
- Pro-active compliance (Product out of EU RoHS legal scope)
Complementary
- Voltage Range
- 208...480 V phase to phase
- Safety Reliability Data
- MTTFd = 502.2 years || B10d = 470000
- Minimum Switching Current
- 10 mA 5 V DC
- Maximum Measuring Cycle
- 150 ms measurement cycle as true rms value
- Control Circuit Voltage Limits
- 12 % + 10 % Un
- Maximum Switching Current
- 5 A AC || 5 A DC
- Hysteresis
- 2-2 %
- Insulation Resistance
- > 500 MOhm 500 V DC IEC 60255-5 || > 500 MOhm 500 V DC IEC 60664-1
- Measurement Error
- < 0.05 %/°C with temperature variation || < 1 % over the whole range with voltage variation
- Operating Rate
- <= 360 operations/hour full load
- Phase Failure Sensitivity
- 0.7 Un
- Power Consumption In Va
- 0-22 VA 400 V AC 50 Hz
- Output Contacts
- 1 C/O
- Adjustment Of Asymmetry Threshold
- 5...15 % of Un selected
- Marking
- CE
- Response Time
- < 200 ms (in the event of a fault)
- Operating Position
- any position without derating
- Utilisation Category
- AC-12 IEC 60947-5-1 || AC-13 IEC 60947-5-1 || AC-14 IEC 60947-5-1 || AC-15 IEC 60947-5-1 || DC-12 IEC 60947-5-1 || DC-13 IEC 60947-5-1
- Net Weight
- 0.13 kg
- Maximum Switching Voltage
- 250 V AC || 250 V DC
- Measurement Voltage Limits
- 183-528 V AC
- Reset Time
- 1500 ms time delay
- Connections - Terminals
- screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end || screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end || screw terminals, 1 x 0.2...1 x 2.5 mm² AWG 24...AWG 12) flexible with cable end || screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end
- [Ui] Rated Insulation Voltage
- 400 V IEC 60664-1
- Overvoltage Category
- III IEC 60664-1
- Supply Voltage Limits
- 183-528 V AC
- Mounting Support
- 35 mm symmetrical DIN rail conforming to IEC 60715
- Nominal Output Current
- 5 A
- Local Signalling
- for power ON LED (green) || for relay ON LED (yellow)
- Mechanical Durability
- 30000000 cycles
- Housing Material
- self-extinguishing plastic
- Control Circuit Frequency
- 50...60 Hz +/- 10 %
- Threshold Adjustment Voltage
- +2...+10 % in the range 480 V AC || 2...20 % of Un selected || -2...-17 % in the range 220 V AC || -2...-12 % in the range 208 V AC
- Width
- 17.5 mm
- Tightening Torque
- 0.6-1 N.m IEC 60947-1
- Electrical Durability
- 100000 cycles
- Run-Up Delay At Power-Up
- 650 ms
- Supply Frequency
- 50/60 Hz +/- 10 %
- Repeat Accuracy
- 0.5 % input and measurement circuit || 3 % time delay
Specifications
- Range Of Product
- Harmony Control Relays
- Measurement Range
- 208...480 V voltage AC
- Switching Capacity In Va
- 1250 VA
- Product Or Component Type
- 3-phase control relay
- Relay Name
- RM17TA
- Contacts Type And Composition
- 1 C/O
- Relay Type
- multifunction control relay
- Product Specific Application
- for 3-phase supply
- Time Delay Type
- adjustable 0.1...10 s, +/- 10 % of the full scale value
- Relay Monitored Parameters
- asymmetry || phase sequence || phase failure detection
- [Uc] Control Circuit Voltage
- 208...480 V
CAD Models
traceparts
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther