Schneider Electric
VLS1P040D1S
1 / 5
Description
Active Mature
These TeSys VLS disconnect switches are for integration into control systems in applications like material handling, HVAC, pumping, solar energy, mining and many more. This family of disconnect switches has switches ranging from 16A to 125A. The 16A, 25A, 32A, 40A and 63A disconnect switches are UL508 motor disconnect switches rated. The 30A, 63A, 80A, 100A and 125A disconnect switches are UL98 non fusible disconnect switch rated. This fourth pole adder can be added to a VLS3P016R1, VLS3P025R1, VLS3P032R1 or VLS3P040R1 door mount switch. This fourth pole adder for door mounted devices can be mounted on the right or left hand side. This simultaneous closing adder pole has one normally open contact The operational voltage of this fourth pole adder module is 600 Vac 50/60 Hz. This fourth pole adder module has a 40 A current rating. The screw clamp terminals will accept 18 AWG to 6 AWG wire. Fourth pole adder is 3.07 inches tall, 0.47 inches wide and 1.72 inches deep. It weighs 0.09 lbs. This fourth pole adder block is cULus Listed and meets IEC 60947-3 requirements.- Country of Origin
- IT
- Part Number
- VLS1P040D1S
- Tariff Code
- 85369095
- EAN
- 3606481156648
- UNSPSC
- 39122233
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Specifications
- Network Frequency
- 50/60 Hz
- Network Type
- AC
- Range Compatibility
- TeSys TeSys VARIO LS VLS3P
- Product Or Component Type
- additional pole
- Performance Level
- high performance
- Range
- TeSys
- Contacts Type And Composition
- 1 NO
- Suitability For Isolation
- yes
- Contact Operation
- simultaneous
- Poles Description
- 1P
- Device Short Name
- VLS1P
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Toxic Heavy Metal Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
- Reach Free Of Svhc
- Yes
- China Rohs Regulation
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Eu Rohs Directive
- Compliant
Complementary
- [Ue] Rated Operational Voltage
- 690 V AC 50/60 Hz
- Height
- 78 mm
- Intermittent Duty Class
- class 120 - 60 %
- [Ith] Conventional Free Air Thermal Current
- 40 A (at 55 °C)
- Mounting Support
- door
- [Ithe] Conventional Enclosed Thermal Current
- 40 A
- Net Weight
- 0.04 kg
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV
- Making Capacity
- 60 A 690 V AC-21A || 120 A 690 V AC-22A || 400 A 690 V AC-23A
- Mounting Location
- right || left
- Connections - Terminals
- power circuit screw clamp terminals 10-10 mm² solid || power circuit screw clamp terminals 16-16 mm² flexible - without cable end
- [Icm] Rated Short-Circuit Making Capacity
- 1128 A 690 V
- Electrical Durability
- 100000 cycles AC-21A
- [Ie] Rated Operational Current
- 40 A Ue: 600 V UL 508 || 40 A AC-21A Ue: 400 V || 40 A AC-21A Ue: 500 V || 40 A AC-21A Ue: 690 V || 40 A AC-22A Ue: 400 V || 40 A AC-22A Ue: 500 V || 40 A AC-22A Ue: 690 V || 40 A AC-23A Ue: 400 V || 25 A AC-23A Ue: 500 V || 25 A AC-23A Ue: 690 V
- Mechanical Durability
- 100000 cycles
- Color
- Gray
- Width
- 12 mm
- Tightening Torque
- power circuit 1.8-2 N.m screw clamp terminals
- Depth
- 43.6 mm
- Breaking Capacity
- 60 A 690 V AC-21A) || 120 A 690 V AC-22A) || 320 A 690 V AC-23A)
- Rated Operational Power In W
- 18.5 kW 400 V AC-23A) || 18.5 kW 500 V AC-23A) || 22 kW 690 V AC-23A)
- Rated Conditional Short-Circuit Current
- 50 kA 400 V 40 A gG
- [Icw] Rated Short-Time Withstand Current
- 800 A 690 V 1 s
Environment
- Product Certifications
- cULus || GL
- Ambient Air Temperature For Operation
- -25-55 °C
- Standards
- UL 508 || CSA C22.2 No 14 || IEC 60947-3
- Ip Degree Of Protection
- IP20 conforming to IEC 60529
- Mechanical Robustness
- vibrations 2...100 Hz Fc 0.7 g) IEC 60068-2-6 || shocks 11 ms Ea 15 gn) IEC 60068-2-27
- Fire Resistance
- 960 °C IEC 60695-2-11
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther