- Alarms
- 8 alarms with configurable thresholds (low/high)
- Frequency accuracy
- Class 0.02
- Frequency range
- 45-65 Hz
- Frequency rating
- 50/60 Hz
- General measurements
- Multi-measurement
- Measurement level
- Power Quality Analysis
- Measurement updating period
- Configurable from 200ms to 60s
- Network type
- To be configured in the module
- Power Quality measurements
- THD V1, V2, V3, U12, U23, U31
- Voltage connection
- Removable screw terminal, 4 positions, AWG 10 to AWG 32 / 0.2 to 2.5 mm² stranded or solid cable
- Voltage measurement accuracy
- Class 0.2
- Voltage measurement range Ph/N
- 50-300VAC
- Voltage measurement range Ph/Ph
- 87-520VAC
- Voltage measurement type
- AC
- Voltage Sampling rate
- 9.6 kHz
- Voltage transformer primary
- To be configured
- Voltage transformer secondary
- To be configured