Rittal
SK 3311.392
1 / 1
Description
Closed loop in row direct expansion cooling unit efficiently maintains proper server inlet temperatures contained entirely within the rack system.- Part Number
- SK 3311.392
- Get up to 90 days payment terms from 500+ suppliers
- Reselling discounts up to 40%!
Send request for price
1
Payment methods:
Air throughput (unimpeded air flow)
- At 50 Hz
- 4,800 m³/h ( 2,825.2cfm )
Dimensions
- Width
- 300 mm ( 12" )
- Height
- 2,000 mm ( 79" )
- Depth
- 1,200 mm ( 47" )
Temperature range
- Storage
- -20 °C...+60 °C
- Operation (environment)
- +15 °C...+35 °C
Specifications
- Function principle
- The LCP draws in the air at the sides at the rear of the server enclosures, cools it using high-performance compact impellers, and blows the cooled air back into the front part of the server enclosure at the sides
- Color
- RAL 9005
- Protection category IP to IEC 60 529
- IP 20
- Note
- Ethernet cable 2482.720 required with SNMP network card 3311.320
- Variant
- Row Cooling
- Number of fan modules in supplied state
- 4
- Total cooling output
- 20 kW
- Rated operating voltage
- 208 V, 1~, 60 Hz
- Installation in bayed enclosure suite
- Flush
- Type of connection (electrical)
- Connection clamp
- Duty cycle
- 100 %
- EC fan
- yes
- Fans may be exchanged with the system operational
- yes
- ECl@ss 8.0/8.1
- 27180712
- ECl@ss 6.0/6.1
- 27180712
Refrigerant/cooling medium
- Cooling medium
- R410a
Modulation range
- Device modulates without interruption in the cooling output range between
- 6 kW - 20 kW
Other Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther