Rittal

SK 3311.392

1 / 1
thumbnail

Description

Closed loop in row direct expansion cooling unit efficiently maintains proper server inlet temperatures contained entirely within the rack system.
Part Number
SK 3311.392
  • Get up to 90 days payment terms from 500+ suppliers
  • Reselling discounts up to 40%!
Sign-Up
Send request for price
1
Payment methods:
Request a Quote and we will send you information on availability and price.

Air throughput (unimpeded air flow)

At 50 Hz
4,800 m³/h ( 2,825.2cfm )

Dimensions

Width
300 mm ( 12" )
Height
2,000 mm ( 79" )
Depth
1,200 mm ( 47" )

Temperature range

Storage
-20 °C...+60 °C
Operation (environment)
+15 °C...+35 °C

Specifications

Function principle
The LCP draws in the air at the sides at the rear of the server enclosures, cools it using high-performance compact impellers, and blows the cooled air back into the front part of the server enclosure at the sides
Color
RAL 9005
Protection category IP to IEC 60 529
IP 20
Note
Ethernet cable 2482.720 required with SNMP network card 3311.320
Variant
Row Cooling
Number of fan modules in supplied state
4
Total cooling output
20 kW
Rated operating voltage
208 V, 1~, 60 Hz
Installation in bayed enclosure suite
Flush
Type of connection (electrical)
Connection clamp
Duty cycle
100 %
EC fan
yes
Fans may be exchanged with the system operational
yes
ECl@ss 8.0/8.1
27180712
ECl@ss 6.0/6.1
27180712

Refrigerant/cooling medium

Cooling medium
R410a

Modulation range

Device modulates without interruption in the cooling output range between
6 kW - 20 kW