Schneider Electric
LC1D65E7
1 / 2
Description
Active Mature
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 65A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance. Contactor is rated for 20HP at 200 to 208VAC, 20HP at 240VAC, 40HP at 480VAC and 50HP at 600VAC three phase. Contactor is also rated for 5HP at 115VAC and 10HP at 240VAC single phase. When used with a 480VAC up to 110A circuit breaker, this contactor can have a SCCR up to 100kA. When used with up to a 600VAC 125A Class J or CC fuse, this contactor can have a SCCR up to 100kA. Contactor is supplied with a 48 VAC 50/60 Hz coil. Contactor has one normally open and one normally closed auxiliary contact built-in as standard. The NC contact is mirror certified. Screw clamp terminals are used for load and auxiliary connections. An extensive line of accessories makes it easy to meet the requirements of most applications. The contactor is 4.80 inches tall, 2.17 inches wide and 4.72 inches deep. It weighs 1.90 lbs. Contactor is certified to UL, CSA, IEC, CCC, EAC and Marine standards. Contactor also meets the requirements of RoHS/REACh making it a Green Premium product.- Country of Origin
- CZ
- Part Number
- LC1D65E7
- Tariff Code
- 8536490065
- EAN
- 39121529
- UNSPSC
- 39121529
£204.07
net1
Payment methods:
- Best offer from:
- Trusted Automa.Net Supplier
- Availability:
- 1 pc.In-StockUpdated at: 21-11-2024
- Estimated Delivery:
- On Request
- Condition:
- New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Shipping Information
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies
Environment
- Product Certifications
- GOST || CCC || UL || DNV || RINA || LROS (Lloyds register of shipping) || BV || GL || UKCA
- Height
- 127 mm
- Standards
- IEC 60947-4-1 || IEC 60947-5-1 || EN 60947-4-1 || CSA C22.2 No 14 || UL 508
- Climatic Withstand
- IACS E10 exposure to damp heat
- Net Weight
- 2.185 kg
- Flame Retardance
- V1 conforming to UL 94
- Ip Degree Of Protection
- IP2X VDE 0106 || IP2X IEC 60529
- Mechanical Robustness
- shocks contactor closed 15 Gn for 11 ms) || vibrations contactor opened 2 Gn, 5...300 Hz) || vibrations contactor closed 4 Gn, 5...300 Hz) || shocks contactor opened 10 Gn for 11 ms)
- Operating Altitude
- 0...9842.52 ft (0...3000 m)
- Fire Resistance
- 850 °C IEC 60695-2-1
- Width
- 85 mm
- Depth
- 176 mm
Contractual warranty
- Warranty
- 18 months
Offer Sustainability
- Rohs Exemption Information
- Yes
- Mercury Free
- Yes
- Environmental Disclosure
- ENVPEP110205EN
- Sustainable Offer Status
- Green Premium product
- Pvc Free
- Yes
- Toxic Heavy Metal Free
- Yes
- Reach Regulation
- Free of Substances of Very High Concern above the threshold
- California Proposition 65
- WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
- Reach Free Of Svhc
- Yes
- Weee
- The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
- China Rohs Regulation
- Pro-active China RoHS declaration (out of China RoHS legal scope)
- Circularity Profile
- N/A
- Eu Rohs Directive
- Compliant
Complementary
- Non-Overlap Time
- 1.5 ms on energisation between NC and NO contacts || 1.5 ms on de-energisation between NC and NO contacts
- Minimum Switching Current
- 5 mA for control circuit
- Power Dissipation Per Pole
- 6.4 W AC-1 || 4.2 W AC-3e || 4.2 W AC-3
- Auxiliary Contact Composition
- 1 NO + 1 NC
- [Ith] Conventional Free Air Thermal Current
- 80 A (at 60 °C) for power circuit || 10 A (at 60 °C) for control circuit
- Control Circuit Voltage Limits
- 0.8...1.1 Uc -40-60 °C operational AC 50 Hz || 0.85...1.1 Uc -40-60 °C operational AC 60 Hz || 1...1.1 Uc 60-70 °C operational AC 50/60 Hz || 0.75...1.25 Uc -40-60 °C operational DC || 0.1...0.3 Uc -40-70 °C drop-out DC
- Mounting Support
- rail
- Control Circuit Type
- DC standard
- Safety Reliability Level
- B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 || B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
- Hold-In Power Consumption In W
- 7.4-7.4 W 20 °C
- Insulation Resistance
- > 10 MOhm for control circuit
- Rated Breaking Capacity
- 1000 A at 440 V for power circuit conforming to IEC 60947
- Irms Rated Making Capacity
- 140 A AC for control circuit conforming to IEC 60947-5-1 || 1000 A at 440 V for power circuit conforming to IEC 60947 || 250 A DC for control circuit conforming to IEC 60947-5-1
- Associated Fuse Rating
- 125 A gG at <= 690 V coordination type 2 for power circuit || 160 A gG at <= 690 V coordination type 1 for power circuit conforming to IEC 60947-5-1 || 10 A gG for control circuit conforming to IEC 60947-5-1
- Inrush Power In Va
- 160-160 VA cos phi 0.75 (at 20 °C)
- [Uimp] Rated Impulse Withstand Voltage
- 8 kV IEC 60947
- Pole Contact Composition
- 3 NO
- Connections - Terminals
- control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: rigid without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || power circuit: screw terminals 1 2.5-25 mm² - cable stiffness: rigid || power circuit: screw terminals 2 2.5-16 mm² - cable stiffness: rigid without cable end || power circuit: screw terminals 1 2.5-25 mm² - cable stiffness: flexible without cable end || power circuit: screw terminals 2 2.5-16 mm² - cable stiffness: flexible without cable end || power circuit: screw terminals 1 2.5-25 mm² - cable stiffness: flexible with cable end || power circuit: screw terminals 2 2.5-10 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: rigid || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: rigid
- Coil Technology
- built-in bidirectional peak limiting diode suppressor
- Time Constant
- 34 ms
- Operating Time
- 12...26 ms closing || 50 ms closing || 20 ms opening
- Minimum Switching Voltage
- 17 V for control circuit
- Maximum Operating Rate
- 3600 cyc/h 60 °C
- Tightening Torque
- control circuit 1.7 N.m screw clamp terminal Philips No 2 || power circuit 5 N.m screw terminal flat Ø 6 to Ø 8 mm || control circuit 1.7 N.m screw clamp terminal pozidriv No 2 || control circuit 1.7 N.m screw clamp terminal flat Ø 6 mm
- Mechanical Durability
- 10000000 cycles
- Inrush Power In W
- 19-19 W 20 °C)
- Auxiliary Contacts Type
- mirror contact 1 NC IEC 60947-4-1 || mechanically linked 1 NO + 1 NC IEC 60947-5-1
- Compatibility Code
- LC1D
- Hold-In Power Consumption In Va
- 15-15 VA 50 Hz cos phi 0.3 (at 20 °C)
- Overvoltage Category
- III
- Maximum Horse Power Rating
- 10 hp at 230/240 V AC 60 Hz for 1 phase motors || 20 hp at 200/208 V AC 60 Hz for 3 phase motors || 20 hp at 230/240 V AC 60 Hz for 3 phase motors || 40 hp at 460/480 V AC 60 Hz for 3 phase motors || 50 hp at 575/600 V AC 60 Hz for 3 phase motors || 5 hp at 115 V AC 60 Hz for 1 phase motors
- Motor Power Kw
- 11 kW at 400 V AC 50 Hz (AC-4) || 30 kW at 380...400 V AC 50 Hz (AC-3) || 37 kW at 500 V AC 50 Hz (AC-3) || 37 kW at 660...690 V AC 50 Hz (AC-3) || 18.5 kW at 220...230 V AC 50 Hz (AC-3) || 30 kW at 415 V AC 50 Hz (AC-3) || 37 kW at 1000 V AC 50 Hz (AC-3) || 30 kW at 440 V AC 50 Hz (AC-3e) || 30 kW at 380...400 V AC 50 Hz (AC-3e) || 37 kW at 500 V AC 50 Hz (AC-3e) || 37 kW at 660...690 V AC 50 Hz (AC-3e) || 18.5 kW at 220...230 V AC 50 Hz (AC-3e) || 30 kW at 415 V AC 50 Hz (AC-3e) || 37 kW at 1000 V AC 50 Hz (AC-3e) || 30 kW at 440 V AC 50 Hz (AC-3)
- [Ui] Rated Insulation Voltage
- control circuit 600 V UL || power circuit 600 V CSA || power circuit 600 V UL IEC 60947-1 || control circuit 690 V IEC 60947-1 || power circuit 690 V CSA IEC 60947-1 || control circuit 600 V CSA
- Rated Operational Power In W
- 12 W 48 V DC-13 10000000 cycles - control circuit || 38 W 48 V DC-13 3000000 cycles - control circuit
- Protective Cover
- with
Specifications
- [Uc] Control Circuit Voltage
- 48 V DC
- [Ue] Rated Operational Voltage
- power circuit <= 690 V AC 25...400 Hz
- Range Of Product
- TeSys Deca
- Contactor Application
- motor control
- Product Or Component Type
- contactor
- Range
- TeSys
- Utilisation Category
- AC-2 || AC-1 || AC-3 || AC-3e
- [Ie] Rated Operational Current
- 65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit || 65 A (at <60 °C) at <= 440 V AC AC-3e for power circuit || 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
- Poles Description
- 3P
- Device Short Name
- LC1D
Documents
Data Sheet
DownloadOther Categories
ActuatorsBlocksCables, Pipes & HosesCompressorsControlCouplings & FittingsCylinders & PistonsElectronicsFiltersHVACIndustrial PC's & HMIsLightingLinear techniqueMotorsPower SupplyPower TransmissionPumps & ValvesRenewable energyRoboticsSeals, Rings & ConnectorsSensors & Measuring DevicesTools and AccessoriesCNCOther