1 / 1
thumbnail

Description

Active Mature
TeSys D pre-assembled star-delta starter, for motor control applications up to 11kW@400V in delta connection. Plate mounted starter, open version, composed of 3 contactors LC1D with 230V 50/60Hz AC coils, 1NC built-in auxiliary contact on star, a time-delay contact block 1-30 sec. For operating rates until 30 starts/hour, maximum starting time 30 sec. Compact assembly (144mm width), screw fixing. Equipped with pre-wired star delta power connections, and mechanical interlock, the use of a thermal overload relay (to be ordered separately) is strongly recommended. Green Premium compliant (RoHS/REACh).
Country of Origin
FR
Part Number
LC3D180AP7
Tariff Code
85371098
EAN
3389110549706
UNSPSC
39121529
€400.00
net
1
Payment methods:
Best offer from:
JOTrusted Automa.Net Supplier
Availability:
1 pc.
In-Stock
Updated at: 27-08-2024
Estimated Delivery:
On Request
Condition:
New Factory Sealed
New Factory Sealed - A brand-new, unused, unopened, undamaged item in its original manufacturer-sealed packaging.
A total of 12 Parts In-Stock from 3 Distributors
Delivery from:
JO
JO
SK
SK
DE
DE
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Available Offers (2)

LC3D180AP7 product image
Schneider Electric

LC3D180AP7

Condition:
New Factory Sealed
Available:
10 pcs.
In-Stock
Updated at: 21-11-2024
Offer from:
SKTrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
LC3D180AP7 product image
Schneider Electric

LC3D180AP7

Condition:
New Surplus
Available:
1 pc.
In-Stock
Updated at: 21-11-2024
Offer from:
DETrusted Automa.Net Supplier
Estimated Delivery:
On Request
Warranty:
12 months
1
Offer with manufacturer lead time
Ships in:On Request
Best price:
€193.82

Environment

Mechanical Robustness
vibrations contactor open2 Gn, 5...300 Hz || vibrations contactor closed4 Gn, 5...300 Hz || shocks contactor open10 Gn for 11 ms || shocks contactor closed15 Gn for 11 ms
Ambient Air Temperature For Operation
-40-70 °C at Uc
Climatic Withstand
IACS E10 || IEC 60947-1 Annex Q category D
Pollution Degree
3
Insulation Resistance
> 10 MOhm for signalling circuit
Flame Retardance
V1 conforming to UL 94
Ambient Air Temperature For Storage
-60-80 °C
Protective Treatment
TH IEC 60068-2-30
Ip Degree Of Protection
IP20 front face IEC 60529
Operating Altitude
9842.52 ft (3000 m) without derating
Fire Resistance
850 °C IEC 60695-2-1

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP1501004
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Toxic Heavy Metal Free
Yes
Reach Regulation
Free of Substances of Very High Concern above the threshold
California Proposition 65
WARNING: This product can expose you to chemicals including: Antimony oxide & Antimony trioxide, which is known to the State of California to cause cancer. For more information go to www.P65Warnings.ca.gov
Reach Free Of Svhc
Yes
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Pro-active China RoHS declaration (out of China RoHS legal scope)
Circularity Profile
ENVEOLI1501004
Eu Rohs Directive
Compliant

Complementary

Non-Overlap Time
1.5 ms on de-energisation between NC and NO contact || 1.5 ms on energisation between NC and NO contact
Minimum Switching Current
5 mA for signalling circuit
Height
124 mm
Control Circuit Voltage Limits
drop-out: 0.3...0.6 Uc at 50/60 Hz (at <60 °C) || operational: 0.8...1.1 Uc at 50 Hz (at <60 °C) || operational: 0.85...1.1 Uc at 60 Hz (at <60 °C)
Starting Time
30 s
Net Weight
1.73 kg
Inrush Power In Va
70-70 VA 60 Hz cos phi 0.75 (at 20 °C) || 70-70 VA 50 Hz cos phi 0.75 (at 20 °C)
Connections - Terminals
control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible without cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 2 1-2.5 mm² - cable stiffness: flexible with cable end || control circuit: screw clamp terminals 1 1-4 mm² - cable stiffness: solid without cable end || control circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminals 1 1.5-6 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: flexible without cable end || power circuit: screw clamp terminals 1 1-6 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 2 1-4 mm² - cable stiffness: flexible with cable end || power circuit: screw clamp terminals 1 1.5-6 mm² - cable stiffness: solid without cable end || power circuit: screw clamp terminals 2 1.5-6 mm² - cable stiffness: solid without cable end
Coil Technology
without built-in suppressor module
Maximum Operating Rate
30 cyc/h 60 °C
Signalling Circuit Frequency
25...400 Hz
Tightening Torque
power circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || power circuit 1.7 N.m screw clamp terminals Philips No 2 || control circuit 1.7 N.m screw clamp terminals flat Ø 6 mm || control circuit 1.7 N.m screw clamp terminals Philips No 2 || power circuit 1.7 N.m screw clamp terminals pozidriv No 2 || control circuit 1.7 N.m screw clamp terminals pozidriv No 2
Auxiliary Contacts Type
mechanically linked IEC 60947-5-1 3 x 1 NO + 1 NC || mirror contact IEC 60947-4-1 3 x 1 NC
Hold-In Power Consumption In Va
7.5-7.5 VA 60 Hz cos phi 0.3 (at 20 °C) || 7-7 VA 50 Hz cos phi 0.3 (at 20 °C)
Switching Voltage
17 V signalling circuit
Width
144 mm
Depth
143 mm
Heat Dissipation
2-3 W 50/60 Hz

Specifications

Product Certifications
DNV || CSA || RINA || LROS (Lloyds register of shipping) || GOST || UL || CCC || GL || BV
Interlocking Type
mechanical
[Uc] Control Circuit Voltage
230 V AC 50/60 Hz
[Ue] Rated Operational Voltage
power circuit <= 690 V AC 25...400 Hz
Standards
EN 60947-4-1 || EN 60947-5-1 || IEC 60947-4-1 || IEC 60947-5-1 || CSA C22.2 No 14 || UL 508 || IEC 60335-1
Pole Contact Composition
3 x 3 NO
Mounting Support
rail
Control Circuit Type
AC 50/60 Hz
Contactor Application
motor control
Product Or Component Type
star delta starter
Product Name
TeSys Deca
[Uimp] Rated Impulse Withstand Voltage
8 kV IEC 60947
Range
TeSys || TeSys Deca
Device Presentation
pre-wired
Utilisation Category
AC-3
[Ie] Rated Operational Current
18 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Auxiliary Contact Composition
1 NC KM1 star contactor
Electrical Durability
1.65 Mcycles 18 A AC-3 <= 440 V
Provided Equipment
protective cover
Overvoltage Category
III
Motor Power Kw
11 kW 220/230 V AC 50/60 Hz || 22 kW 415 V AC 50/60 Hz || 22 kW 440 V AC 50/60 Hz || 18.5 kW 380/400 V AC 50/60 Hz
[Ui] Rated Insulation Voltage
power circuit 600 V CSA || power circuit 600 V UL || signalling circuit 600 V CSA || signalling circuit 600 V UL || power circuit 1000 V IEC 60947-4-1 || signalling circuit 1000 V IEC 60947-1
Device Short Name
LC3D
Poles Description
3 x 3P