1 / 1
thumbnail

Description

Active Mature
TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This controller is the central component in the motor management system. The module manages the basic functions of the motor management system. It manages the measurement of 3 phase current via integral current transformers from 0.4 to 100 A or up to 810 A by external current transformers. It also measures ground current with internal or external ground sensors, motor temperature and the inputs and outputs for the various motor control modes, detected fault management and other functions. DeviceNet protocol is used by this controller. This module has 6 discrete logic inputs, 3 relay logic outputs and a relay output for detected fault signaling overload relay. The current range of this controller is 0.4 to 8 amperes. 24 VDC is used to power this controller. Controller is 2.40 inches tall, 3.58 inches wide and 4.82 inches deep. Controller weighs 1.17 lbs. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.
Country of Origin
CN
Part Number
LTMR08DBD
Tariff Code
85371091
EAN
3389119404747
UNSPSC
39122214
€355.50
net
€395.00
Shipping from:
€40.00
1
Payment methods:
Best offer from:
DETrusted Automa.Net Supplier
Availability:
2 pcs.
In-Stock
Updated at: 22-11-2024
Warranty:
24 months
Estimated Delivery:
03-05 December to United Kingdom
Condition:
New Surplus
New Surplus - A new, unused, undamaged item without a manufacturer guarantee. The item may come without original packaging or in replacement packaging. If provided, the box may have been opened.
Secure Payment Process
Return & Refund Policies
Shipping Policies
Warranty Policies

Environment

Product Certifications
LROS (Lloyds register of shipping) || DNV || GL || UL || C-tick || BV || CSA || ATEX || RINA || KERI || CCC || ABS || EAC || RMRoS || NOM
Mechanical Robustness
vibrations mounted on symmetrical rail1 Gn, 5...300 Hz EN/IEC 60068-2-6 || vibrations plate mounted4 Gn, 5...300 Hz EN/IEC 60068-2-6 || shocks half sine wave acceleration15 Gn for 11 ms EN/IEC 60068-2-27
Ambient Air Temperature For Operation
-20-60 °C
Standards
EN 60947-4-1 || CSA C22.2 No 14 || UL 508 || IACS E10 || IEC 60947-4-1
Ambient Air Temperature For Storage
-40-80 °C
Protective Treatment
12 x 24 hour cycles EN/IEC 60068-2-30 || 48 h EN/IEC 60070-2-11 || TH EN/IEC 60068
Operating Altitude
<= 6561.68 ft (2000 m) without derating
Fire Resistance
650 °C EN/IEC 60695-2-12 || 960 °C UL 94
Ip Degree Of Protection
IP20

Contractual warranty

Warranty
18 months

Offer Sustainability

Rohs Exemption Information
Yes
Mercury Free
Yes
Environmental Disclosure
ENVPEP060308EN_V2
Sustainable Offer Status
Green Premium product
Pvc Free
Yes
Reach Regulation
Reference contains Substances of Very High Concern above the threshold
Weee
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
China Rohs Regulation
Product out of China RoHS scope. Substance declaration for your information.
Circularity Profile
ENVEOLI100411EN_V2
Eu Rohs Directive
Compliant with Exemptions
Halogen Content Performance
Halogen free plastic parts product

Complementary

Contacts Type And Composition
1 NO + 1 NC fault signal || 3 NO
Height
61 mm
Connection Pitch
5.08 mm
Permissible Power
480 VA AC-15), Ie = 2 A, 500000 cycles output) || 30 W DC-13), Ie = 1.25 A, 500000 cycles output)
Network And Machine Diagnosis Type
fault recording || waiting time after overload tripping || remaining operating time before overload tripping || phase fault and earth fault trip counters || starting current and time || trip history information || trip context information || motor control command recording || running hours counter/operating time || event recording
Pollution Degree
3
Logic Input Number
6
Maximum Operating Rate
1800 cyc/h
Connections - Terminals
control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.25-2.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 1 0.2-2.5 mm² AWG 24...AWG 14)solid without cable end || control circuit connector 2 0.2-1 mm² AWG 24...AWG 14)flexible with cable end || control circuit connector 2 0.2-1.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 2 0.5-1.5 mm² AWG 24...AWG 14)flexible without cable end || control circuit connector 2 0.2-1 mm² AWG 24...AWG 14)solid without cable end
Input Current
7 mA
Current State 1 Guaranteed
logic input < 15 V 2...15 mA 15 ms
Net Weight
0.53 kg
[Uimp] Rated Impulse Withstand Voltage
6 kV current or voltage measurement circuit EN/IEC 60947-4-1 || 0.8 kV communication circuit EN/IEC 60947-4-1 || 0.8 kV supply, inputs and outputs EN/IEC 60947-4-1
Associated Fuse Rating
4 A gG output || 0.5 A gG control circuit
Electromagnetic Compatibility
electrostatic discharge, 3, 8 kV air, 6 kV contact, conforming to EN/IEC 61000-4-2 || control circuit: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || communication: surges (common mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (serial mode), 2 kV, conforming to EN/IEC 61000-4-5 || relay outputs and supply: surges (common mode), 4 kV, conforming to EN/IEC 61000-4-5 || radiated RF fields, 3, 10 V/m, conforming to EN/IEC 61000-4-3 || fast transients immunity test (other circuits), level 3, 2 kV, conforming to EN/IEC 61000-4-4 || fast transients immunity test (on supply and relay outputs), level 4, 4 kV, conforming to EN/IEC 61000-4-4 || voltage dips and interruptions immunity test, 70 %, 500 ms, conforming to EN/IEC 61000-4-11 || conducted RF disturbances, 10 V, conforming to EN/IEC 61000-4-6 || temperature sensor: surges (serial mode), 0.5 kV, conforming to EN/IEC 61000-4-5 || temperature sensor: surges (common mode), 1 kV, conforming to EN/IEC 61000-4-5 || control circuit: surges (serial mode), 1 kV, conforming to EN/IEC 61000-4-5
Measurement Accuracy
5...15 % earth fault current internal measurement || 1 % voltage 100...830 V) || 3 % power factor || 5 % earth fault current external measurement || +/- 30 min/year internal clock || 0,02 Temperature || 1 % current || 5 % active and reactive power
Current State 0 Guaranteed
logic input < 5 V <= 15 mA 5 ms
[Ui] Rated Insulation Voltage
690 V EN/IEC 60947-1 || 690 V CSA C22.2 No 14 || 690 V UL 508
Short-Circuit Withstand
100 kA conforming to EN/IEC 60947-4-1
Compatibility Code
LTMR
Protection Type
thermal overload protection || overload || power factor variation || reverse polarity protection || earth-leakage protection || thermal protection || overload (long time) || phase failure || load fluctuation || phase unbalance || locked rotor
Web Services
web server
Width
91 mm
Load Current
5 A 250 V AC logic output || 5 A 30 V DC logic output
Tightening Torque
control circuit 0.5-0.6 N.m flat 3 mm
Overvoltage Category
III
Depth
122.5 mm
Maximum Operating Frequency
2 Hz
Metering Type
phase current I1, I2, I3 RMS || temperature || earth-fault current || average current Iavg || imbalance current

Specifications

Product Or Component Type
motor controller
Product Name
TeSys T
Measurement Current
0.4-8 A
Range
TeSys
Current Consumption
56...127 mA
[Us] Rated Supply Voltage
24 V DC
Communication Port Protocol
DeviceNet
Bus Type
DeviceNet ISO 1198 1...64 125...500 kbit/s, terminal block 4 twisted shielded pairs cable
Supply Voltage Limits
20.4-26.24 V DC
Device Application
equipment monitoring and control
Device Short Name
LTMR

CAD Models

traceparts
traceparts
Download